Parameters on Display Level 1
p Proportional Band Setting
i Integral Time Setting
d Derivative Time Setting
ofr Manual Reset Value
Setting
It is possible to set the proportional band within a range of 0.1 to 999.9 C/ F.
It is possible to set the integral time within a range of 0 to 3999 s.
It is possible to set the derivative time within a range of 0 to 3999 s.
It is possible to set the necessary output value when the E5jJ is in constant op-
eration within a range of 0.0% to 100.0%. The E5jJ will be balanced with a devi-
ation between the set point and process value in P or PD control mode. This
deviation is called offset. The offset can be removed by changing the manual
reset value.