Commissioning Without Wolf Control Accessories (Bm) - Wolf COB Technical Manual And Installation Instructions

Oil condensing boiler for central heating
Table of Contents

Advertisement

Commissioning
Test port
"Inlet air"
0
I
ON/OFF
Temperature
O N / O F F
DHW
switch
selector
3062547_201802
32 Commissioning without Wolf
control accessories (BM)
Only qualified personnel must carry out the commissioning and operation of the
boiler and instruct the user!
Check the boiler and system for water tightness. If water tightness
Test port
Note
cannot be ensured, there is a risk of leaking water causing water
"Flue gas"
damage. Normal operating pressure when system is cold 1.5 - 2.0 bar.
Check the oil level in the tank. Commissioning without oil may damage
Note
the oil pump, due to dry running.
Check the system for oil leaks. Prevent oil leaks. If oil tightness is not
assured, there is a risk to health from drinking water which has been
contaminated with oil
Check the water level in the trap. Operating the appliance with an empty
trap presents a risk of poisoning due to flue gases escaping.
- Check that all flue gas accessories have been correctly installed.
Operating the appliance with a leaking flue gas system presents a risk
of poisoning or asphyxiation due to the escape of flue gases.
- Fit casing.
- Open the shut-off valves in the flow and return.
- Open oil shut-off valves (tank, oil line, filter).
- Switch on the heating emergency stop switch.
60
40
80
20
100
°C
0
120
- Switch on the system ON/OFF switch on the control unit.
- Remove cap from l.h. test port (inlet air).
- Insert test probe 2 cm.
Temperature
Heating water
- Turn DHW temperature selector to 1.
selector
- Turn heating water temperature selector to "Emissions test"
(illuminated signal ring flashes yellow)
- After a pre-purge time of approx. 25 sec., the pump starts up and opens the solenoid
valve. The drawn fuel oil reaches the nozzle and a flame builds.
- The burner enters a fault state if, during commissioning, the oil pump does not supply
sufficient oil during the pre-purge time. Repeat the burner start by pressing reset.
- Measure temperature and CO
report (see the commissioning report chapter).
- The flue is not gas tight if the CO
- Terminate the emissions test mode by turning the temperature selector back to its
original position.
- If emissions test mode is not reset manually, the appliance switches back to the
original operating mode automatically after 15 minutes.
- Remove the test probe and close the test port. Ensure the cap is seated firmly.
in the inlet air and enter the values in the commissioning
2
content > 0.2%; rectify the leak.
2
51