Hg Control Parameters - Wolf CGB-2 Service Instructions Manual

Gas condensing boilers
Table of Contents

Advertisement

Modifications must only be carried out by a recognised heating contractor or by Wolf customer service.
Please
Incorrect operation can lead to system faults.
note
On the AM display module or the BM2 programming unit, the factory setting for the HG parameters can be
Please
reinstated in the Contractor menu.
note
To prevent damage to the heating system, cancel night setback when outside temperatures fall below -12 °C.
Failure to observe this requirement may result in ice forming on the flue outlet which may cause injury or
material losses.
The control parameters can only be modified or displayed using the AM display module or BM-2 programming unit on the boiler.
For procedures, check the operating instructions of the relevant accessories.
No.:
Designation:
HG01
Burner switching hysteresis
HG02
Lower burner output, heat generator in % (fan control)
HG03
Upper burner output, DHW (fan control)
Maximum burner output, DHW in %
HG04
Upper burner output, heating (fan control)
Maximum burner output, heating in %
HG07
Heating circuit pump run-on time
Heating circuit pump run-on time in heating mode
HG08
Max. boiler temp., heating (applies to heating mode) TV-max
HG09
Burner cycle block, applies to heating mode
HG10
Heat generator eBUS address
HG12
Gas type
HG13
Function, input E1
Various functions can be assigned to input E1.
HG14
Function, output A1 (230 V AC)
Various functions can be assigned to output A1.
HG15
Cylinder hysteresis, switching differential during cylinder reheating
HG16
HC Pump rate, minimum
HG17
HC pump rate, maximum
HG19
Run-on time, CLP (cylinder loading pump)
HG20
Max. cylinder heating time
HG21
Minimum boiler temperature TK-min
HG22
Maximum boiler temperature TK-max
HG23
Maximum hot water temperature
HG25
Boiler excess temperature during cylinder heating
HG33
Burner hysteresis runtime
HG34
eBUS feed
HG37
Pump control type (constant/linear/dT)
HG38
Set spread, pump control (dT)
HG39
Soft start time
HG40
System configuration (see chapter "Parameter description")
HG41
ZHP speed DHW
HG42
Hysteresis, header
HG43
IO reduction, default value
HG44
GPV curve offset
HG45
No function
HG46
Excess boiler temperature, header
HG60
Minimum burner switching hysteresis
HG61
DHW control unit (boiler sensor / header sensor)
Minimum boiler output
1)
CGB-2-14 = 2.5 %
2)
3)
Value is set automatically with GLV adaptation
24
17. HG control parameters
Unit
Factory setting
Condensing boiler
14 kW
20 kW
24 kW
°C
12
12
%
26
24
%
100
100
%
100
88
min
1
1
°C
80
80
min
7
7
-
1
1
-
Nat.
Nat.
gas
gas
-
none
none
-
none
none
°C
5
5
%
30
30
%
70
70
min
3
3
min
120
120
°C
20
20
°C
85
85
°C
65
65
°C
15
15
min
10
10
-
Auto
Auto
-
Lin.
Lin.
°C
15
15
min
3
3
-
01
01
%
65
75
°C
5
5
-
0
0
%
29,6
30,9
30,9
3)
3)
-
-
-
°C
6
6
°C
7
7
-
Boiler
Boiler
Boiler
sensor
sensor
sensor
Min:
Max:
12
7
30
24
100
1)
100
1)
100
88
100
1)
1
0
30
80
40
90
7
1
30
1
1
5
Nat.
Nat.
LPG
gas
gas
none
var.
var.
none
var.
var.
5
1
30
30
15
100
70
15
100
3
1
10
120
30/Off
180
20
20
90
85
50
90
65
50
90
15
1
30
10
1
30
Auto
OFF
ON
Lin.
var.
var.
15
0
40
3
0
10
01
var.
var.
85
15
100
5
0
20
0
-5
10
15
46.4
3)
-
-
-
6
0
20
7
2
30
Various Various
3064812_201804