Installation instructions

DHW cylinders TSW-120/CSW-120
for gas-fired condensing boilers and
conventional gas-fired boilers
Wolf GmbH · Postfach 1380 · 84048 Mainburg · Tel. 08751/74-0 · Fax 08751/741600 · Internet: www.wolf-heiztechnik.de
Installation instructions DHW cylinders TSW-120/CSW-120
1
Part no. 30 48 420
07/07
GB
3048420_0707

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TSW-120 and is the answer not in the manual?

Questions and answers

Summary of Contents for Wolf TSW-120

  • Page 1: Installation Instructions

    Installation instructions DHW cylinders TSW-120/CSW-120 for gas-fired condensing boilers and conventional gas-fired boilers Wolf GmbH · Postfach 1380 · 84048 Mainburg · Tel. 08751/74-0 · Fax 08751/741600 · Internet: www.wolf-heiztechnik.de Installation instructions DHW cylinders TSW-120/CSW-120 Part no. 30 48 420 07/07...
  • Page 2: Table Of Contents

    - expansion valve with check valve - tundishes - pipes - connection supplies 3) Box containing expansion vessel Don’t stack the packages. Don’t transport lying. Handle and store Keep the packages in dry conditions. Installation instructions DHW cylinders TSW-120/CSW-120 3048420_0707...
  • Page 3: Safety Notice / Dhw Cylinders / Standards And Regulations

    Note: The discharge could consist of scalding water and steam. DHW cylinders, type TSW-120 / CSW-120, made from steel with DHW cylinders top flange and pipework connections for gas-fired boilers.
  • Page 4: Specification

    Specification The safety system of the DHW cylinder TSW-120/CSW-120 is attuned to use only in combination with Wolf boiler TGG-18, TGG- 24 and TGB-20. Specification Type of DHW cylinder TSW/CSW -120 Cylinder capacity litres Const. DHW cyl. rating (80/60 - 10/45°C) kW-ltrs./h 29-710 Standby consumption at 60°C...
  • Page 5: Dimensions

    Dimensions Filling and draining for TSW-120 below the decorative panel DHW circulation Cold water DHW return Domestic hot water DHW cylinder flow Sensor well Fig.: TSW-120 Fig.: CSW-120 Installation instructions DHW cylinders TSW-120/CSW-120 3048420_0707...
  • Page 6: Layout

    Cold water to cylinder Expansion vessel Expansion valve with discharge outlet to tundish Check valve Pressure reducing valve Stop valve Drain The layout is provided to provide a general overview, not a piping Please note: prescription. Installation instructions DHW cylinders TSW-120/CSW-120 3048420_0707...
  • Page 7: Positioning / Installation Dimensions

    Install appliance as described in Installation Instructions. The installation dimensions apply to TSW-120 as well as CSW-120. Please note when using If you intend installing the DHW cylinder with a pipe cover, check the...
  • Page 8: Installation

    DHW cylinder Remove the blue dummy plug from the control unit and connect temperature sensor with the socket of the DHW cylinder temperature sensor. Insert the sensor into the sensor well until it bottoms out. Installation instructions DHW cylinders TSW-120/CSW-120 3048420_0707...
  • Page 9: Installation Of The Tundish

    Note: The discharge will consist of scalding water and steam. Asphalt, roofing felt and non-metallic rainwater goods may be damaged by such discharges. Installation instructions DHW cylinders TSW-120/CSW-120 3048420_0707...
  • Page 10 14 m at 0.8 m each = 3.2 m As the actual length is 7 m, a 28 mm (D2) Therefore the maximum permitted length equates copper pipe will be satisfactory. to: 5.8 m. Installation instructions DHW cylinders TSW-120/CSW-120 3048420_0707...
  • Page 11: Installation Of The Tundish

    22/18 expansion valve with check valve plug pressure tundish reducing domestic DO NOT USE THIS TUNDISH valve cold WITH THE P+T-VALVE water hold a distance of 25mm between the tundish and the pipe end. Installation instructions DHW cylinders TSW-120/CSW-120 3048420_0707...
  • Page 12: Installation Of The Domestic Water Connection

    Installation of the domestic water connetoin View of complete mounted DHW cylinder with tundish and domestic water connection View of complete mounted DHW cylinder with tundish, domestic water connection and connection accessory to the boiler Installation instructions DHW cylinders TSW-120/CSW-120 3048420_0707...
  • Page 13 Install the DHW cylinder so that it can be removed without Drain dismantling. The TSW-120 is provided with a drain below the decorative panel. DHW connection - When installing the DHW cylinder ...SW below the gas-fired boiler, use the Wolf accessory “DHW cylinder connection set for...
  • Page 14: Final Assembly

    Please note: Two white plastic plugs are surplus and should be retained as spare parts. On TSW-120 use the white plastic plugs supplied to close the three holes in each of the l.h./r.h. rear side panels. Pipe cover After the installation, locate the pipe cover (accesory) on the DHW cylinder ...SW-120 and push back.
  • Page 15: Circulation / Commissioning

    5) Check that no water is passing to waste through the relief valves; 6) Test the operation of the temperature and pressure relief and expansion valves by lifting/turning the manually operated test lever/cap and observing that water flows through freely and safely to waste. Installation instructions DHW cylinders TSW-120/CSW-120 3048420_0707...
  • Page 16: Circulation / Commissioning

    In hard water areas we recommend thermostat setting 7 (approx. 60°C) to prolong element life. The DHW cylinder temperature can be read off at the display if a Wolf gas-fired boiler is connected to digital control accessories DRT, DWT or DWTM, (see operating instructions of the respective control unit).
  • Page 17: Maintenance

    DHW circulation pump, and open a hot water tap in your house. A hose nozzle is factory-fitted below the fill and drain cock cover. On TSW-120, the decorative panel must first be removed by slightly lifting and pulling it forward.
  • Page 18: Maintenance

    7) Pressure reducing valve - check that the correct outlet pressure is being maintained by recording the pressure at an in-line termi- nal fitted i.e. tap. Installation instructions DHW cylinders TSW-120/CSW-120 3048420_0707...
  • Page 19 Notice Installation instructions DHW cylinders TSW-120/CSW-120 3048420_0707...
  • Page 20 Wolf GmbH · Postfach 1380 · 84048 Mainburg · Tel. 08751/74-0 · Fax 08751/741600 · Internet: www.wolf-heiztechnik.de Installation instructions DHW cylinders TSW-120/CSW-120 3048420_0707...