Installation Instructions
Model MLC
MXL Line Card
INTRODUCTION
OPERATION
A6V10328217_en--_f
The Model MLC MXL Line Card loop driver from Siemens
Industry, Inc., is a module that allows MXL intelligent
addressable smoke detectors, manual stations, monitor
devices, and control devices to interface to the FireFinder-
XLS/Desigo Fire Safety Modular/Cerberus PRO Modular
System. The MLC uses two consecutive addresses on the
HNET network. The application program that is loaded into
the on-board microprocessor controls the MLC operation. An
XLS/Desigo Fire Safety Modular/Cerberus PRO Modular
system can support a maximum of 2500 MXL intelligent
field devices using up to 25 MLC cards.
The MLC contains nine diagnostic LEDs. Ground fault
detection is provided. A USB port is included to allow
firmware upload via the front panel.
All field devices connected to the MLC are addressed and
tested using the Device Programming Unit (DPU) or the
FPI-21 Programmer/Tester. The select system setting on
the DPU and FPI-32 must be set to MXL.
The MLC initializes, operates, and maintains all devices
residing on the loop. The MLC communicates all relevant
device and event information, such as alarms and troubles,
to the PMI/PMI-2/PMI-3 (XLS), FCM2041-U2 (Desigo Fire
Safety Modular), FCM2041-U3 (Cerberus PRO Modular).
The sensitivity of any intelligent smoke detector and the
logic functions of any intelligent output devices can be
checked and adjusted from the PMI/PMI-2/PMI-3 (XLS),
FCM2041-U2 (Desigo Fire Safety Modular), FCM2041-U3
(Cerberus PRO Modular) through the MLC. All information
about the devices on the loop can be displayed on the PMI/
PMI-2/PMI-3 (XLS), FCM2041-U2 (Desigo Fire Safety
Modular), FCM2041-U3 (Cerberus PRO Modular). To see
the available information for each device on the loop, refer
to the FireFinder-XLS IOM Manual, P/N 315-033744, the
Desigo Fire Safety Modular IOM, Document ID A6V11231620,
or the Cerberus PRO Modular IOM, Document ID A6V11231627 .
The MLC supports two separate circuits of MXL intelligent field devices. Each circuit
can monitor and control up to 60 intelligent devices as well as device accessories
(relay bases, audible bases, and remote lamps) in any combination. Each circuit has a
separate address on the HNET network. The installer sets the address on the module
for the first circuit which can be either odd or even. A consecutive address is auto-
matically assigned to the second circuit internally.
MLC
RESET
POWER
CARD FAIL
HNET FAIL
ALARM
TROUBLE
MAIN CIRCUITS
TROUBLE
GND FAULT
EXP CIRCUITS
TROUBLE
GND FAULT
HUNDREDS
TENS
ONES
HNET
Figure 1
MLC Line Card
Siemens
Siemens
Industry
Industry, , , , , Inc.
Industry
Siemens Industry
Siemens
Siemens
Industry
Building
Building
Building T T T T T ec
Building
Building
ec
ec
echnologies Di
ec
hnologies Di
hnologies Di
hnologies Di
hnologies Division
USB
Inc.
Inc.
Inc.
Inc.
vision
vision
vision
vision

Advertisement

Table of Contents
loading

Summary of Contents for Siemens MLC

  • Page 1 Desigo Fire Safety Modular IOM, Document ID A6V11231620, or the Cerberus PRO Modular IOM, Document ID A6V11231627 . The MLC supports two separate circuits of MXL intelligent field devices. Each circuit can monitor and control up to 60 intelligent devices as well as device accessories (relay bases, audible bases, and remote lamps) in any combination.
  • Page 2 Fire Safety Modular), FCM2041-U3 (Cerberus PRO Modular) fails. Controls and Indicators The front panel of the MLC contains one reset switch, 9 LEDs, and three HNET address switches, as shown in Figure 1. Pushing the reset switch re-initializes the MLC operation.
  • Page 3: Pre-Installation

    (Refer TENS to Figure 1 for the location of the switches.) The address for the MLC must be the ONES same as the address selected for it in the Zeus Programming Tool. To set the address, HNET turn the pointers on each of the three dials to the numbers for the selected address.
  • Page 4 Disconnect the USB cable and reset the module. Find MLC Software Version To check for the current version of MLC software in an installed MLC, go to the PMI/ PMI-2/PMI-3 (XLS), FCM2041-U2 (Desigo Fire Safety Modular), FCM2041-U3 (Cerberus PRO Modular) and press the Menu button, select Report, press the More Info button and select the MLC at that address.
  • Page 5: Class A Wiring

    RS-485 and other data circuits. Do not mix MLC and DLC circuits in the same conduit if the wire is untwisted and the run length exceeds 2000 feet. Electrical connections for the two loops are shown in Figure 4. Each device loop circuit can be independently wired in either Class A or Class B configuration.
  • Page 6 The MLC supports two device loops of up to 60 intelligent field devices each. Each loop draws a maximum of 90mA from the MLC. All circuits are power limited per NEC 760. The MLC supports the use of 12- 18 AWG non-shielded, non-twisted, thermoplastic fixture wire without conduit, if permitted by local building codes.
  • Page 7 Time (sec), ” as shown in Figure 5. f i r i l a i n r i l a i n r i l a i n r i l a i n r Siemens Industry, Inc. A6V10328217_en--_f Building Technologies Division...
  • Page 8: Electrical Ratings

    Detectors with “Not Compatible”shown in Table 3 cannot be used with the CZM-1/-1B6 alarm verification feature, but can be used when alarm verification is disabled. Each detector is assigned a category. Do not mix detectors from different categories on the same circuit. ELECTRICAL RATINGS Siemens Industry, Inc. A6V10328217_en--_f Building Technologies Division...
  • Page 9: Cyber Security Disclaimer

    Generally, these embedded free software files are distributed in the hope that they will be useful, but WITHOUT ANY WARRANTY, without even implied warranty such as for MERCHANTABILITY or FITNESS FOR A PARTICULAR PURPOSE, and without liability for any Siemens entity other than as explicitly documented in your purchase contract.
  • Page 10 P/N A5Q00066395 Document ID A6V10328217_en--_f Siemens Industry, Inc. Siemens Canada, Ltd. Building Technologies Division 1577 North Service Road East Florham Park, NJ Oakville, Ontario L6H 0H6 Canada...

Table of Contents