6 Commissioning
6.2.2

Selection of command source

Selection of
P0700 =...
command source
Selects digital command source.
0
Factory fault setting
1
BOP (keypad)
2
Terminal
4
USS on BOP link
5
USS on COM link
6
CB on COM link
6.2.3

Digital input (DIN)

Function of digital input 1
P0701=...
Terminal 5
1
ON / OFF1
Function digital input 2
P0702 =...
Terminal 6
12
Reverse
Function digital input 3
P0703 =...
Terminal 7
9
Fault acknowledge
Function digital input 4
P0704 = 0
Via analog input
Terminals 3, 4
0
Digital input disabled
Debounce time for
P0724 =...
digital inputs
Defines debounce time (filtering
time) used for digital inputs.
0
No debounce time
1
2.5 ms debounce time
2
8.2 ms debounce time
3
12.3 ms debounce time
DIN channel
16
2
BOP
Terminals
USS
BOP link
USS
COM link
CB
COM link
1
Possible Settings:
0
Digital input disabled
1
ON / OFF1
2
ON + Reverse / OFF1
12
3
OFF2 – coast to standstill
4
OFF3 – quick ramp-down
9
Fault acknowledge
10
JOG right
9
11
JOG left
12
Reverse
13
MOP up (increase frequency)
0
14
MOP down (decrease frequency)
15
Fixed setpoint (Direct selection)
16
Fixed setpoint (Direct selection + ON)
17
Fixed setpoint (Binary coded selection + ON)
21
Local/remote
3
25
DC brake enable
29
External trip
33
Disable additional freq setpoint
99
Enable BICO parameterization
Kl.8 P24
Debounce time: DIN
0 ... 3
Kl.9 0 V
P0724 (3)
24 V
T
0
0 V
Issue 04/04
P0700 = 2
Sequence control
Setpoint
channel
Function of DIN 1
0 ... 99
P0701 (1)
0
&
99
r0722
r0722
CO/BO: Bin.inp.val
MICROMASTER 420
Compact Operating Manual
Motor
control