How To Set Up The Cooling Only Indoor Unit - Toshiba MMU-AP0091H Owner's Manual Installation And Operation

Super heat recovery multi system
Hide thumbs Also See for MMU-AP0091H:
Table of Contents

Advertisement

9

HOW TO SET UP THE COOLING ONLY INDOOR UNIT

When setting the specific indoor unit to Cooling Only unit without connecting to the flow selector unit, setup to the
indoor unit to become the Cooling Only unit is necessary.
Perform setup in the following procedure.
Setup to the indoor unit is performed by handling the wired remote controller.
Even if a wired remote controller is not used, attach a wired remote controller for setup.
When using the air conditioner with a wireless remote controller, select "Cooling Only" of the wireless remote
controller after the above setup.
For handling the wireless remote controller, refer to the manual attached to the wireless remote controller.
Change the setup during stop of the operation.
(Be sure to stop operation of the air conditioner.)
Procedure
When pushing
flashes as shown in the figure.
Check that the displayed item code is [10].
1
• If the item code indicates one other than [10], push
erase the display, and then retry the operation from the first step.
(After pushing
controller cannot be accepted after a while.)
In a group control, the firstly displayed indoor unit No. becomes the header unit.
Every pushing [UNIT] button, the indoor unit No. in the group control is displayed successively.
2
Select an indoor unit of which setup is to be changed.
In this time, the position of the indoor unit of which setup is to be changed
can be confirmed because the fan and flap of the selected indoor unit work.
3
Use
and
Use
and
4
Setup data
Cooling Only setup
SET
Push
button. In this time, if the display changes from flashing to lighting, the setup completes.
• To change the setup of an indoor unit other than the selected one, start operation from Procedure
• In a group control, setup change of all the indoor units in a group is necessary.
5
To change the setup of the set other than the selected one, start again operation from Procedure
CAUTION
CL
• Pushing
• In this case, retry from Procedure 2 .
When the setup finished, push
TEST
Pushing
6
(For some time after
remote controller cannot be accepted.)
SET
CL
TEST
+
+
buttons simultaneously for 4 seconds or more, after a while, the display part
TEST
button, the operation of remote
buttons of the set temperature to specify the item code [0F].
buttons of the timer time to select the setup data [0001].
0000
Heat pump
Cooling Only and Heat pump cannot exist in the same group.
button clears the set up contents which have been already set.
TEST
button. (The setup is determined.)
button deletes the display and returns to normal stop status.
TEST
button has been pushed, the operation of the
TEMP.
4
TIMER SET
1
TIME
FILTER
RESET TEST
SET CL
6
Description
TEST
button to
(* The display changes according to the indoor unit model.)
0001
Cooling Only
60
CODE No.
UNIT No.
R.C.
No.
ON / OFF
3
FAN
MODE
2
SWING/FIX
VENT
UNIT
5
SETTING
UNIT No.
R.C.
No.
UNIT No.
∗∗ ∗∗
R.C.
No.
2
2
CODE No.
CODE No.
.
.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents