Toshiba MMU-AP0091H Owner's Manual Installation And Operation page 77

Super heat recovery multi system
Hide thumbs Also See for MMU-AP0091H:
Table of Contents

Advertisement

Pipe forming/End positioning
Flaring
1. Cut the pipe with a pipe cutter.
2. Insert a flare nut into pipe, and flare the pipe.
As the flaring sizes of R410A differ from those of refrigerant R22, the flare tools newly manufactured for R410A
are recommended.
However, the conventional tools can be used by adjusting projection margin of copper pipe.
A
B
Connection of refrigerant pipe
Connect all the refrigerant pipes with flare connecting
work.
• Since the atmospheric pressure only is sealed as the
sealing gas, it is not abnormal that "Pushu..." sound
is not heard when the flare nut is removed.
• Be sure use a double spanner for pipe connecting
work of the indoor unit.
Work using double spanner
Flaring diam. Meter size: A (Unit: mm)
Outer diam. of
copper pipe
9.5
12.7
15.9
Projection margin in flaring: B (Unit: mm)
Rigid (Clutch type)
Outer diam. of
copper pipe
9.5
12.7
15.9
Imperial (Wing nut type)
Outer diam. of copper pipe
9.5
12.7
15.9
+0
A
- 0.4
R410A
R22
13.2
13.0
16.6
16.2
19.7
19.2
R410A tool used
R410A
R22
0 to 0.5
(Same as left)
0 to 0.5
(Same as left)
0 to 0.5
(Same as left)
R410A
1.5 to 2.0
2.0 to 2.5
2.0 to 2.5
• Refer to the following table for tightening torque.
Connecting pipe
outer diam. (mm)
Ø9.5
Ø12.7
Ø15.9
Ø19.1
If an excessive torque is applied, the nut may
crack depending on the installation conditions.
74
90˚
Obliquity
Roughness
* In case of flaring for R410A with the
conventional flare tool, pull it out
approx. 0.5mm more than that for R22
to adjust to the specified flare size.
The copper pipe gauge is useful for
adjusting projection margin size.
Conventional tool used
R410A
1.0 to 1.5
1.0 to 1.5
1.0 to 1.5
R22
1.0 to 1.5
1.5 to 2.0
1.5 to 2.0
Tightening
torque (N•m)
33 to 42
(3.3 to 4.2 kgf•m)
50 to 62
(5.0 to 6.2 kgf•m)
68 to 82
(6.8 to 8.2 kgf•m)
98 to 118
(10 to 12 kgf•m)
REQUIREMENT
Warp
R22
0.5 to 1.0
0.5 to 1.0
0.5 to 1.0
Re-tightening
torque (N•m)
42 (4.2 kgf•m)
50 (5.0 kgf•m)
68 (6.8 kgf•m)
98 (10 kgf•m)

Hide quick links:

Advertisement

Table of Contents
loading