How to set up the cooling only indoor unit

When setting the specific indoor unit to Cooling Only
unit without connecting to the flow selector unit, setup
to the indoor unit to become the Cooling Only unit is
necessary. Perform setup in the following procedure.
Setup to the indoor unit is performed by handling the
wired remote controller.
Even if a wired remote controller is not used, attach a
wired remote controller for setup.
Change the setup with the wired remote controller
before using the air conditioner with a wireless remote
controller.
Change the setup during stop of the operation.
(Be sure to stop operation of the air conditioner.)
SET
DATA
SETTING
No.
4
1
6
5
2
1
When pushing
+
+
buttons
simultaneously for 4 seconds or more,
after a while, the display part flashes as
shown in the figure.
Check that the displayed CODE No. is [10].
• If the CODE No. indicates one other than [10],
push
button to erase the display, and then
retry the operation from the first step.
(After pushing
button, the operation of
remote controller cannot be accepted after a
while.)
SET
DATA
SETTING
SETTING
UNIT No.
R.C.
No.
(* The display changes according to the indoor unit
model.)
73-EN
AMP Air Conditioning
2
In a group control, the firstly displayed
indoor unit No. becomes the header unit.
Every pushing
button (left side of the
button), the indoor unit No. in the group control is
displayed successively.
Select an indoor unit of which
setting is to be changed.
SET
DATA
SETTING
SETTING
UNIT No.
R.C.
No.
In this time, the position of the indoor unit of
which setup is to be changed can be confirmed
because the fan and louver of the selected
indoor unit work.
3
3
Use
and
buttons of the set
temperature to specify the CODE No. [0F].
4
Use
and
buttons of the timer time to
select the setup data [0001].
SET DATA
0000
Cooling Only
Heat pump
setup
5
Push
button. In this time, if the display
changes from flashing to lighting, the
setup completes.
• To change the setup of an indoor unit other
than the selected one, start operation from
2
Procedure
.
• In a group control, setup change of all the
indoor units in a group is necessary.
To change the setup of the set other than
the selected one, start again operation from
2
Procedure
.
CAUTION
CODE No.
Cooling Only and Heat pump cannot exist in the
same group.
• Pushing
button clears the set up contents
which have been already set.
In this case, retry from Procedure
– 3 7 –
6
When the setup finished, push
(The setup is determined.)
Pushing
button deletes the display and
returns to normal stop status.
(For some time after
the operation of the remote controller cannot be
accepted.)
CODE No.
0001
Cooling Only
2
.
button.
button has been pushed,
www.ampair.co.uk | sales@ampair.co.uk