Building Automation
3
Commissioning
the PXM10
The PXM10 is used for local operation of a compact or
modular DESIGO PX automation station. No user login is
required. The PXM10 allows you to work at the "Basic" and
"Standard" operating levels.
All the objects from these operating levels are mapped in the
device.
"Favorite" objects are defined at the engineering stage and
mapped separately.
Step
Action
1
Mount the PXM10 on the housing of the modular
automation station.
or
Connect the PXM10 to the compact or modular
automation station with a PXA-C1 cable.
2
After a few seconds, the display will light up and
the opening screen will appear. The PXM10 is now
ready for operation:
Figure 3-1 Opening screen
3
Either open the plant data with OK
or
Press the alarm button to go directly to the alarm
list.
The PXM10 and PXM20 can be used in parallel for operation
and monitoring of a PXC...-U automation station by
mounting the PXM10 directly on the automation station and
connecting the PXM20 to the MMI/tool socket with a PXA-C1
cable.
PXM10 operator unit
CM110397en
31.08.2004