Grounding for Host Interface

Figure 4.5: Location of ground jumper RS-485 host interface
The jumper setting A1 shows the factory settings.
Jumper JP1 connects the internal ground of the AMC2-4W to
the ground of the RS-485 host interface.
Jumper JP2 manages the signal ground.
Settings for jumper JP1:
If the ground conductor and the shield on the host are not
connected and ...
Settings for jumper JP2:
If the ground conductor and the shield on the host are not
connected and ...
Bosch Sicherheitssysteme
no party line exists, the jumper JP1 is set (= A2)
a party line exists, the jumper JP1 is set at the first device,
only (= A2)
no party line exists, the jumper 2 is set (= A3)
a party line exists and signal ground is connected, the
jumper 2 is set at the first device, only (= A3)
a party line exists and signal ground is not connected, the
jumper 2 is set at all devices (= A3)