ABB REL650 Product Manual page 65

Line distance protection
Hide thumbs Also See for REL650:
Table of Contents

Advertisement

Line distance protection REL650 ANSI
Product version: 1.3
Logic
Table 66. Tripping logic common 3-phase output SMPPTRC (94)
Function
Trip action
Timers
Table 67. Tripping logic phase segregated output SPTPTRC (94)
Function
Trip action
Timers
Table 68. Configurable logic blocks
Logic block
Quantity
with cycle
time
5 ms
AND
60
OR
60
XOR
10
INVERTER
30
SRMEMORY
10
RSMEMORY
10
GATE
10
PULSETIMER
10
TIMERSET
10
LOOPDELAY
10
ABB
Range or value
3-ph
(0.000-60.000) s
Range or value
3-Ph, 1/3-Ph
(0.000-60.000) s
Range or value
20 ms
100 ms
60
160
-
60
160
-
10
20
-
30
80
-
10
20
-
10
20
-
10
20
-
10
20
(0.000–90000.000) s
10
20
(0.000–90000.000) s
10
20
Accuracy
-
± 0.5% ± 10 ms
Accuracy
-
± 0.5% ± 10 ms
1MRK 506 337-BUS B
Accuracy
-
-
-
-
-
-
-
± 0.5% ± 25 ms for 20
ms cycle time
± 0.5% ± 25 ms for 20
ms cycle time
65

Advertisement

Table of Contents
loading

Table of Contents