ABB REL650 Product Manual page 50

Line distance protection
Hide thumbs Also See for REL650:
Table of Contents

Advertisement

Line distance protection REL650 ANSI
Product version: 1.3
Table 34. Four step phase overcurrent protection, phase segregated output OC4SPTOC (51_67)
Function
Operate current
Reset ratio
Min. operating current
Independent time delay
Minimum operate time for inverse
characteristics
Inverse characteristics, see
table 89, table
90
and table
91
Operate time, nondirectional
pickup function
Reset time, pickup function
Operate time, directional pickup
function
Reset time, directional pickup
function
Critical impulse time
Impulse margin time
1)
Note: Timing accuracy only valid when 2nd harmonic blocking is turned off.
Table 35. Instantaneous residual overcurrent protection EFPIOC (50N)
Function
Operate current
Reset ratio
Operate time
Reset time
Critical impulse time
Operate time
Reset time
Critical impulse time
Dynamic overreach
50
Setting range
lBase
(5-2500)% of
> 95%
lBase
(5-10000)% of
(0.000-60.000) s
(0.000-60.000) s
15 curve types
25 ms typically at 0 to 2 x I
set
35 ms typically at 2 to 0 x I
set
50 ms typically at 0 to 2 x I
set
35 ms typically at 2 to 0 x I
set
10 ms typically at 0 to 2 x I
set
15 ms typically
Range or value
(1-2500)% of lBase
> 95%
20 ms typically at 0 to 2 x I
set
30 ms typically at 2 to 0 x I
set
10 ms typically at 0 to 2 x I
set
10 ms typically at 0 to 5x I
set
40 ms typically at 5 to 0x I
set
2 ms typically at 0 to 5 x I
set
< 5% at t = 100 ms
1MRK 506 337-BUS B
Accuracy
± 1.0% of I
at I £ I
n
n
± 1.0% of I at I > I
n
-
± 1.0% of I
at I < I
±1.0% of I at I
n
n
> I
n
± 0.5% ± 25 ms
± 0.5% ± 25 ms
1)
ANSI/IEEE C37.112
IEC 60255–151
±3% or ±40 ms
0.10 ≤ k ≤ 3.00
1.5 x I
≤ I ≤ 20 x I
set
set
-
-
-
-
-
-
Accuracy
± 1.0% of I
at I £ I
n
n
± 1.0% of I at I > I
n
-
-
-
-
-
-
-
-