Table 18. Electromagnetic compatibility tests, continued
Description
Voltage dips and short interruptionsc on DC
power supply
Voltage dips and interruptions on AC power
supply
Electromagnetic emission tests
• Conducted, RF-emission (mains terminal)
0.15...0.50 MHz
0.5...30 MHz
• Radiated RF-emission, ANSI
30 – 88 MHz
88 – 216 MHz
216 – 960 MHz
960 – 1000 MHz
ABB
Type test value
Dips:
40%/200 ms
70%/500 ms
Interruptions:
0-50 ms: No restart
0...∞ s : Correct behaviour at power down
Dips:
40% 10/12 cycles at 50/60 Hz
70% 25/30 cycles at 50/60 Hz
Interruptions:
0–50 ms: No restart
0...∞ s: Correct behaviour at power down
< 79 dB(µV) quasi peak
< 66 dB(µV) average
< 73 dB(µV) quasi peak
< 60 dB(µV) average
< 39,08 dB(µV/m) quasi peak, measured at 10 m
distance
< 43,52 dB(µV/m) quasi peak, measured at 10 m
distance
< 46,44 dB(µV/m) quasi peak, measured at 10 m
distance
< 49,54 dB(µV/m) quasi peak, measured at 10 m
distance
1MRK 506 337-BUS B
Reference
IEC 60255-11
IEC 61000-4-11
IEC 60255–11
IEC 61000–4–11
EN 55011, class A
IEC 60255-25
ANSI C63.4, FCC