ABB REL650 Product Manual page 38

Line distance protection
Hide thumbs Also See for REL650:
Table of Contents

Advertisement

Line distance protection REL650 ANSI
Product version: 1.3
Auxiliary AC and DC voltage
Table 3. Power supply
Description
V
n
V
variation
n
Maximum load of auxiliary voltage
supply
Ripple in the DC auxiliary voltage
Maximum interruption time in the
auxiliary DC voltage without resetting
the IED
Resolution of the voltage
measurement in PSM module
Binary inputs and outputs
Table 4. Binary inputs
Description
Operating range
Rated voltage
Current drain
Power consumption/input
Threshold voltage
Table 5. Signal output and IRF output
IRF relay change over - type signal output relay
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry 0.5 s
Breaking capacity when the control-circuit time constant L/R<40 ms, at V<
48/110/220 V DC
38
600PSM01
24, 30 V DC
80...120% of V
(24...30 V DC)
n
35 W for DC
40 VA for AC
Max 15% of the DC value (at frequency of 100 and 120 Hz)
50 ms at V
n
1 bit represents 0,5 V (+/- 1 VDC)
600PSM02
48, 60, 110, 125 V DC
80...120% of V
(38.4...150 V DC)
n
1 bit represents 1 V (+/- 1 VDC)
Value
Maximum input voltage 300 V DC
24...250 V DC
1.6...1.8 mA
<0.38 W
15...221 V DC (parametrizable in the range in steps of 1% of the rated voltage)
Value
250 V AC/DC
5 A
10 A
30 A
≤0.5 A/≤0.1 A/≤0.04 A
1MRK 506 337-BUS B
600PSM03
100, 110, 120, 220, 240 V AC, 50
and 60 Hz
110, 125, 220, 250 V DC
85...110% of V
(85...264 V AC)
n
80...120% of V
(88...300 V DC)
n
1 bit represents 2 V (+/- 1 VDC)
ABB

Advertisement

Table of Contents
loading

Table of Contents