Carrier 30RB060-390 Installation Instructions Manual page 67

Aquasnap air-cooled chillers and / with greenspeed technology
Hide thumbs Also See for 30RB060-390:
Table of Contents

Advertisement

UNIT VOLTAGE
Supplied
UNIT 30RB
V-Hz (3 Ph)
Min
Max
208/230-60
187
253
380-60
342
418
210
460-60
414
506
575-60
518
633
208/230-60
187
253
380-60
342
418
225
460-60
414
506
575-60
518
633
208/230-60
187
253
380-60
342
418
250
460-60
414
506
575-60
518
633
208/230-60
187
253
380-60
342
418
275
460-60
414
506
575-60
518
633
208/230-60
187
253
380-60
342
418
300
460-60
414
506
575-60
518
633
208/230-60
187
253
380-60
342
418
315A
460-60
414
506
575-60
518
633
208/230-60
187
253
460-60
414
506
315B
575-60
518
633
380-60
342
418
208/230-60
187
253
380-60
342
418
330A
460-60
414
506
575-60
518
633
208/230-60
187
253
380-60
342
418
330B
460-60
414
506
575-60
518
633
208/230-60
187
253
380-60
342
418
345A
460-60
414
506
575-60
518
633
208/230-60
187
253
380-60
342
418
345B
460-60
414
506
575-60
518
633
208/230-60
187
253
380-60
342
418
360A
460-60
414
506
575-60
518
633
208/230-60
187
253
380-60
342
418
360B
460-60
414
506
575-60
518
633
208/230-60
187
253
380-60
342
418
390A
460-60
414
506
575-60
518
633
208/230-60
187
253
380-60
342
418
390B
460-60
414
506
575-60
518
633
LEGEND
AWG
— American Wire Gage
ICF
— Instantaneous Current Flow (Ckt1/Ckt2)
MCA
— Minimum Circuit Amps (Ckt1/Ckt2)
MOCP — Maximum Overcurrent Protection (Ckt1/Ckt2)
XL
— Across-the-Line Start
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit
terminals is not below or above the listed minimum and maximum limits. Maximum
allowable phase imbalance is: voltage, 2%; amps 10%.
2. Control power is derived from main power. No separate control power connection is
required.
3. Cooler heater is wired into the control circuit so it is always operable as long as the
power supply disconnect is on, even if any safety device is open.
4. For MCA that is less than or equal to 380 amps, 3 conductors are required.
For MCA between 381-760 amps, 6 conductors are required.
For MCA between 761-1140 amps, 9 conductors are required.
For MCA between 1141-1520 amps, 12 conductors are required.
Calculation of conductors required is based on 75 C copper wire.
Table 11B — 30RB210-390 Electrical Data — Dual Point Units
NO HYDRONIC PACKAGE
MCA
MOCP
ICF
XL
XL
XL
626.7/353.9
700/400
1068.9/796.2
327.7/186.4
350/225
581.1/439.7
233.3/200.0
250/225
441.3/408.0
188.8/162.0
200/175
356.4/329.6
684.3/353.9
700/400
1126.5/796.2
360.4/186.4
400/225
613.8/439.7
260.0/200.0
300/225
468.0/408.0
211.9/162.0
225/175
379.5/329.6
684.3/472.0
700/500
1126.5/914.3
360.4/248.7
400/250
613.8/502.1
303.2/209.2
350/250
511.2/417.2
246.4/170.0
250/200
414.1/337.6
920.5/353.9 1000/400
1362.7/796.2
485.2/186.4
500/225
738.5/439.7
408.0/156.8
450/175
616.0/364.8
331.5/127.5
350/150
499.1/295.1
920.5/472.0 1000/500
1362.7/914.3
485.2/248.7
500/250
738.5/502.1
408.0/209.2
450/250
616.0/417.2
331.5/170.0
350/200
499.1/337.6
519.8/243.8
600/300
962.0/635.0
274.9/124.8
300/150
528.3/336.8
230.8/106.3
250/125
438.8/280.4
187.3/ 85.2
200/110
354.9/227.4
519.8/243.8
600/300
962.0/635.0
230.8/106.3
250/125
438.8/280.4
187.3/ 85.2
200/110
354.9/227.4
274.9/124.8
300/150
528.3/336.8
519.8/306.2
600/400
962.0/748.4
274.9/160.2
300/200
528.3/413.6
230.8/135.2
250/175
438.8/343.2
187.3/110.2
200/125
354.9/277.8
519.8/243.8
600/300
962.0/635.0
274.9/124.8
300/150
528.3/336.8
230.8/106.3
250/125
438.8/280.4
187.3/ 85.2
200/110
354.9/227.4
519.8/306.2
600/400
962.0/748.4
274.9/160.2
300/200
528.3/413.6
230.8/135.2
250/175
438.8/343.2
187.3/110.2
200/125
354.9/277.8
519.8/306.2
600/400
962.0/748.4
274.9/160.2
300/200
528.3/413.6
230.8/135.2
250/175
438.8/343.2
187.3/110.2
200/125
354.9/277.8
543.7/400.4
600/450
985.9/842.6
288.0/209.5
300/250
541.3/462.9
241.6/176.8
250/200
449.6/384.8
195.9/144.1
225/175
363.5/311.7
519.8/306.2
600/400
962.0/748.4
274.9/160.2
300/200
528.3/413.6
230.8/135.2
250/175
438.8/343.2
187.3/110.2
200/125
354.9/277.8
543.7/400.4
600/450
985.9/842.6
288.0/209.5
300/250
541.3/462.9
241.6/176.8
250/200
449.6/384.8
195.9/144.1
225/175
363.5/311.7
543.7/400.4
600/450
985.9/842.6
288.0/209.5
300/250
541.3/462.9
241.6/176.8
250/200
449.6/384.8
195.9/144.1
225/175
363.5/311.7
3 HP PUMP, 1750 RPM
MCA
MOCP
ICF
Rec Fuse
Size
XL
XL
XL
700/400
350/200
250/225
200/175
700/400
400/200
300/225
225/175
700/500
400/250
350/225
250/200
1000/400
500/200
450/175
350/150
1000/500
500/250
450/225
350/200
600/300
300/150
250/125
200/100
600/300
250/125
200/100
300/150
600/350
300/175
250/150
200/125
600/300
300/150
250/125
200/100
600/350
300/175
250/150
200/125
600/350
300/175
250/150
200/125
600/450
300/225
250/200
225/175
600/350
300/175
250/150
200/125
600/450
300/225
250/200
225/175
600/450
300/225
250/200
225/175
5. Wiring for main field supply must be rated 75 C minimum. Use copper for all units.
a. Incoming wire size range for the terminal block is no. 4 AWG to 500 kcmil.
b. Incoming wire size range of non-fused disconnect with MCA up to 599.9 amps is
3/0 to 500 kcmil.
c. Incoming wire size range of non-fused disconnect with MCA from 600 to
799.9 amps is 1/0 to 500 kcmil.
d. Incoming wire size range of non-fused disconnect with MCA from 800 to
1199.9 amps is 250 kcmil to 500 kcmil.
6. Hydronic pump packages are not available as a factory-installed option for units
30RB210-390.
7. Power draw includes both crankcase heaters and cooler heaters (where used). Each
compressor has a crankcase heater which draws 56 watts of power. Units ordered with
the cooler heater option have 1 (060-150) or 2 (160-300) cooler heaters, 825 watts
each.
67
5 HP PUMP, 1750 RPM
Rec
MCA
MOCP
Fuse
XL
XL
Size
208/230
460
575 v only
ICF
Rec
Fuse
XL
Size

Hide quick links: