Carrier 30RB060-390 Installation Instructions Manual page 63

Aquasnap air-cooled chillers and / with greenspeed technology
Hide thumbs Also See for 30RB060-390:
Table of Contents

Advertisement

Table 10A — 30RB060-190 Electrical Data — Single Point Units (cont)
UNIT VOLTAGE
UNIT 30RB
Supplied
V-Hz (3 Ph)
Min
208/230-60
187
380-60
342
060
460-60
414
575-60
518
208/230-60
187
380-60
342
070
460-60
414
575-60
518
208/230-60
187
380-60
342
080
460-60
414
575-60
518
208/230-60
187
380-60
342
090
460-60
414
575-60
518
208/230-60
187
380-60
342
100
460-60
414
575-60
518
208/230-60
187
380-60
342
110
460-60
414
575-60
518
208/230-60
187
380-60
342
120
460-60
414
575-60
518
208/230-60
187
380-60
342
130
460-60
414
575-60
518
208/230-60
187
380-60
342
150
460-60
414
575-60
518
208/230-60
187
380-60
342
160
460-60
414
575-60
518
208/230-60
187
380-60
342
170
460-60
414
575-60
518
208/230-60
187
380-60
342
190
460-60
414
575-60
518
LEGEND
AWG — American Wire Gage
ICF
— Instantaneous Current Flow
MCA — Minimum Circuit Amps
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit
terminals is not below or above the listed minimum and maximum limits. Maximum
allowable phase imbalance is: voltage, 2%; amps 10%.
2. All units and modules have single point primary power connection. (Each unit or mod-
ule requires its own power supply.) Main power must be supplied from a field-supplied
disconnect.
3. Cooler heater is wired into the control circuit so it is always operable as long as the
power supply disconnect is on, even if any safety device is open.
4. For MCA that is less than or equal to 380 amps, 3 conductors are required.
For MCA between 381-760 amps, 6 conductors are required.
For MCA between 761-1140 amps, 9 conductors are required.
For MCA between 1141-1520 amps, 12 conductors are required.
Calculation of conductors required is based on 75 C copper wire.
7.5 HP PUMP, 1750/3450 RPM
MCA
MOCP
ICF
Max
XL
XL
XL
253
313.5
350
708.5
418
163.2
200
376.9
506
138.0
150
313.6
633
110.5
125
254.0
253
356.7
450
802.7
418
187.8
225
442.8
506
158.0
175
367.5
633
127.9
150
296.7
253
388.5
450
783.5
418
201.6
225
415.3
506
170.7
200
346.3
633
136.7
150
280.2
253
455.6
500
901.6
418
239.2
250
494.3
506
201.5
225
411.0
633
162.7
175
331.5
253
494.0
500
940.0
418
261.0
300
516.1
506
219.3
250
428.8
633
178.1
200
346.9
253
530.6
600
976.6
418
277.6
300
532.7
506
234.2
250
443.7
633
188.9
200
357.7
253
600.1
700
1046.1
418
316.9
350
572.0
506
266.3
300
425.8
633
216.3
225
385.1
253
648.7
700
1094.6
418
340.0
350
595.1
506
286.6
300
496.1
633
231.4
250
400.3
253
706.3
800
1152.2
418
372.7
400
627.8
506
313.3
350
522.8
633
254.5
300
423.4
253
766.8
800
1212.7
418
402.4
450
657.5
506
339.0
350
548.5
633
274.0
300
442.8
253
824.4
1000
1270.3
418
435.1
450
690.2
506
365.7
400
575.2
633
297.1
300
465.9
253
942.5
1000
1388.4
418
497.5
500
752.5
506
418.1
450
627.6
633
339.6
350
508.4
MOCP — Maximum Overcurrent Protection
XL
— Across-the-Line Start
10 HP PUMP, 3450 RPM
MCA
MOCP
ICF
Rec Fuse
Size
XL
XL
XL
350
316.5
350
716.4
175
164.9
200
381.3
150
139.4
150
317.2
125
111.6
125
256.9
400
359.7
450
810.6
225
189.5
225
447.2
175
159.4
200
371.1
150
129.0
150
299.6
450
391.5
450
791.4
225
203.3
225
419.7
200
172.1
200
349.9
150
137.8
150
283.1
500
458.6
500
909.5
250
240.9
250
498.7
225
202.9
225
414.6
175
163.8
175
334.4
500
497.0
500
947.9
300
262.7
300
520.5
250
220.7
250
432.4
200
179.2
200
349.8
600
533.6
600
984.5
300
279.3
300
537.1
250
235.6
250
447.3
200
190.0
200
360.6
700
603.1
700
1054.0
350
318.6
350
576.4
300
267.7
300
479.4
250
217.4
250
388.0
700
651.7
700
1102.5
350
341.7
350
599.5
300
288.0
300
499.7
250
232.5
250
403.2
800
709.3
800
1160.1
400
374.4
400
632.2
350
314.7
350
526.4
300
255.6
300
426.3
800
769.8
800
1220.6
450
404.1
450
661.9
350
340.4
350
552.1
300
275.1
300
445.7
1000
827.4
1000
1278.2
450
436.8
450
694.6
400
367.1
400
578.8
300
298.2
300
468.8
1000
945.5
1000
1396.3
500
499.2
500
756.9
450
419.5
450
631.2
350
340.7
350
511.3
5. Wiring for main field supply must be rated 75 C minimum. Use copper for all units.
a. Incoming wire size range for the terminal block is no. 4 AWG to 500 kcmil.
b. Incoming wire size range of non-fused disconnect with MCA up to 599.9 amps is
3/0 to 500 kcmil.
c. Incoming wire size range of non-fused disconnect with MCA from 600 to
799.9 amps is 1/0 to 500 kcmil.
d. Incoming wire size range of non-fused disconnect with MCA from 800 to
1199.9 amps is 250 kcmil to 500 kcmil.
6. Hydronic pump packages are not available as a factory-installed option for units
30RB210-390.
7. Power draw includes both crankcase heaters and cooler heaters (where used). Each
compressor has a crankcase heater which draws 56 watts of power. Units ordered with
the cooler heater option have 1 (060-150) or 2 (160-300) cooler heaters, 825 watts
each.
63
15 HP PUMP, 3450 RPM
MCA
MOCP
ICF
Rec Fuse
Size
XL
XL
XL
350
175
150
125
400
225
175
150
450
403.2
450
807.6
225
210.3
225
428.5
200
177.6
200
357.2
150
142.6
150
288.9
500
470.3
500
925.7
250
247.9
250
507.5
225
208.4
250
421.9
175
168.6
200
340.2
600
508.7
600
964.1
300
269.7
300
529.3
250
226.2
250
439.7
200
184.0
200
355.6
600
545.3
600
1000.7
300
286.3
300
545.9
250
241.1
250
454.6
200
194.8
225
366.4
700
614.8
700
1070.2
350
325.6
350
585.2
300
273.2
300
486.7
250
222.2
250
393.8
700
663.4
700
1118.7
350
348.7
350
608.3
300
293.5
300
507.0
250
237.3
250
409.0
800
721.0
800
1176.3
400
381.4
400
641.0
350
320.2
350
533.7
300
260.4
300
432.1
800
781.5
800
1236.8
450
411.1
450
670.7
350
345.9
350
559.4
300
279.9
300
451.5
1000
839.1
1000
1294.4
450
443.8
450
703.4
400
372.6
400
586.1
350
303.0
350
474.6
1000
957.2
1000
1412.5
600
506.2
600
765.7
450
425.0
450
638.5
350
345.5
350
517.1
208/230
460
575 v only
Rec Fuse
Size
450
225
200
150
500
300
225
200
600
300
250
200
600
300
250
225
700
350
300
250
700
400
300
250
800
400
350
300
800
450
400
300
1000
500
400
350
1000
600
450
350