Table 11A — 30RB060-190 Electrical Data — Dual Point Units (cont)
UNIT VOLTAGE
30RB
UNIT
Supplied
V-Hz (3 Ph)
SIZE
Min
Max
208/230-60
187
253
190.8/141.5
380-60
342
418
98.7/ 74.1
060
460-60
414
506
83.7/ 62.5
575-60
518
633
67.1/ 50.0
208/230-60
187
253
234.0/141.5
380-60
342
418
123.2/ 74.1
070
460-60
414
506
103.7/ 62.5
575-60
518
633
84.4/ 50.0
208/230-60
187
253
238.5/168.8
380-60
342
418
124.8/ 86.4
080
460-60
414
506
105.3/ 73.6
575-60
518
633
84.3/ 59.0
208/230-60
187
253
305.6/168.8
380-60
342
418
162.4/ 86.4
090
460-60
414
506
136.1/ 73.6
575-60
518
633
110.3/ 59.0
208/230-60
187
253
305.6/212.0
380-60
342
418
162.4/110.9
100
460-60
414
506
136.1/ 93.6
575-60
518
633
110.3/ 76.3
208/230-60
187
253
305.6/243.8
380-60
342
418
162.4/124.8
110
460-60
414
506
136.1/106.3
575-60
518
633
110.3/ 85.2
208/230-60
187
253
317.5/306.2
380-60
342
418
169.0/160.2
120
460-60
414
506
141.5/135.2
575-60
518
633
114.6/110.2
208/230-60
187
253
423.7/243.8
380-60
342
418
224.8/124.8
130
460-60
414
506
188.5/106.3
575-60
518
633
152.8/ 85.2
208/230-60
187
253
423.7/306.2
380-60
342
418
224.8/160.2
150
460-60
414
506
188.5/135.2
575-60
518
633
152.8/110.2
208/230-60
187
253
541.8/243.8
380-60
342
418
287.2/124.8
160
460-60
414
506
240.9/106.3
575-60
518
633
195.4/ 85.2
208/230-60
187
253
541.8/306.2
380-60
342
418
287.2/160.2
170
460-60
414
506
240.9/135.2
575-60
518
633
195.4/110.2
208/230-60
187
253
565.7/400.4
380-60
342
418
300.3/209.5
190
460-60
414
506
251.7/176.8
575-60
518
633
204.0/144.1
LEGEND
AWG
— American Wire Gage
ICF
— Instantaneous Current Flow (Ckt1/Ckt2)
MCA
— Minimum Circuit Amps (Ckt1/Ckt2)
MOCP — Maximum Overcurrent Protection (Ckt1/Ckt2)
XL
— Across-the-Line Start
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit
terminals is not below or above the listed minimum and maximum limits. Maximum
allowable phase imbalance is: voltage, 2%; amps 10%.
2. Control power is derived from main power. No separate control power connection is
required.
3. Cooler heater is wired into the control circuit so it is always operable as long as the
power supply disconnect is on, even if any safety device is open.
4. For MCA that is less than or equal to 380 amps, 3 conductors are required.
For MCA between 381-760 amps, 6 conductors are required.
For MCA between 761-1140 amps, 9 conductors are required.
For MCA between 1141-1520 amps, 12 conductors are required.
Calculation of conductors required is based on 75 C copper wire.
7.5 HP PUMP, 1750/3450 RPM
MCA
MOCP
ICF
Rec Fuse
Size
XL
XL
XL
250/200
585.7/532.8
225/175
125/110
312.4/286.1
110/ 90
110/ 90
259.3/236.6
100/ 80
90/ 70
210.5/192.3
80/ 60
300/200
679.9/532.8
300/175
150/110
378.3/286.1
150/ 90
125/ 90
313.2/236.6
125/ 80
110/ 70
253.2/192.3
100/ 60
300/225
633.4/560.0
300/200
150/110
338.6/298.4
150/100
125/100
280.9/247.7
125/ 90
110/ 80
227.8/201.2
100/ 70
350/225
751.5/560.0
350/200
200/110
417.6/298.4
175/100
175/100
345.6/247.7
150/ 90
125/ 80
279.1/201.2
125/ 70
350/300
751.5/654.2
350/250
200/150
417.6/364.3
175/125
175/125
345.6/301.6
150/110
125/110
279.1/243.9
125/ 90
350/300
751.5/635.0
350/300
200/150
417.6/336.8
175/150
175/125
345.6/280.4
150/125
125/110
279.1/227.4
125/100
400/400
763.5/748.4
350/350
200/200
424.1/413.6
200/175
175/175
351.0/343.2
175/150
125/125
283.4/277.8
125/125
500/300
869.6/635.0
450/300
250/150
479.9/336.8
250/150
225/125
398.0/280.4
200/125
175/110
321.6/227.4
175/100
500/400
869.6/748.4
450/350
250/200
479.9/413.6
250/175
225/175
398.0/343.2
200/150
175/125
321.6/277.8
175/125
600/300
987.7/635.0
600/300
300/150
542.3/336.8
300/150
250/125
450.4/280.4
250/125
225/110
364.2/227.4
225/100
600/400
987.7/748.4
600/350
300/200
542.3/413.6
300/175
250/175
450.4/343.2
250/150
225/125
364.2/277.8
225/125
600/450 1011.6/842.6
600/450
350/250
555.4/462.9
350/225
300/200
461.2/384.8
300/200
225/175
372.8/311.7
225/175
10 HP PUMP, 3450 RPM
MCA
MOCP
ICF
XL
XL
XL
193.8/141.5
250/200
593.6/532.8
100.4/ 74.1
125/110
316.8/286.1
85.1/ 62.5
110/ 90
262.9/236.6
68.2/ 50.0
90/ 70
213.4/192.3
237.0/141.5
300/200
687.8/532.8
124.9/ 74.1
150/110
382.7/286.1
105.1/ 62.5
125/ 90
316.8/236.6
85.5/ 50.0
110/ 70
256.1/192.3
241.5/168.8
300/225
641.4/560.0
126.5/ 86.4
150/110
342.9/298.4
106.7/ 73.6
125/100
284.5/247.7
85.4/ 59.0
110/ 80
230.6/201.2
308.6/168.8
400/225
759.5/560.0
164.1/ 86.4
200/110
421.9/298.4
137.5/ 73.6
175/100
349.2/247.7
111.4/ 59.0
125/ 80
282.0/201.2
308.6/212.0
400/300
759.5/654.2
164.1/110.9
200/150
421.9/364.3
137.5/ 93.6
175/125
349.2/301.6
111.4/ 76.3
125/110
282.0/243.9
308.6/243.8
400/300
759.5/635.0
164.1/124.8
200/150
421.9/336.8
137.5/106.3
175/125
349.2/280.4
111.4/ 85.2
125/110
282.0/227.4
320.5/306.2
400/400
771.4/748.4
170.7/160.2
200/200
428.5/413.6
142.9/135.2
175/175
354.6/343.2
115.7/110.2
125/125
286.3/277.8
426.7/243.8
500/300
877.6/635.0
226.5/124.8
250/150
484.3/336.8
189.9/106.3
225/125
401.6/280.4
153.9/ 85.2
175/110
324.5/227.4
426.7/306.2
500/400
877.6/748.4
226.5/160.2
250/200
484.3/413.6
189.9/135.2
225/175
401.6/343.2
153.9/110.2
175/125
324.5/277.8
544.8/243.8
600/300
995.6/635.0
288.9/124.8
300/150
546.7/336.8
242.3/106.3
250/125
454.0/280.4
196.5/ 85.2
225/110
367.1/227.4
544.8/306.2
600/400
995.6/748.4
288.9/160.2
300/200
546.7/413.6
242.3/135.2
250/175
454.0/343.2
196.5/110.2
225/125
367.1/277.8
568.7/400.4
600/450 1019.5/842.6
302.0/209.5
350/250
559.7/462.9
253.1/176.8
300/200
464.8/384.8
205.1/144.1
225/175
375.7/311.7
5. Wiring for main field supply must be rated 75 C minimum. Use copper for all units.
a. Incoming wire size range for the terminal block is no. 4 AWG to 500 kcmil.
b. Incoming wire size range of non-fused disconnect with MCA up to 599.9 amps is
3/0 to 500 kcmil.
c. Incoming wire size range of non-fused disconnect with MCA from 600 to
799.9 amps is 1/0 to 500 kcmil.
d. Incoming wire size range of non-fused disconnect with MCA from 800 to
1199.9 amps is 250 kcmil to 500 kcmil.
6. Hydronic pump packages are not available as a factory-installed option for units
30RB210-390.
7. Power draw includes both crankcase heaters and cooler heaters (where used). Each
compressor has a crankcase heater which draws 56 watts of power. Units ordered with
the cooler heater option have 1 (060-150) or 2 (160-300) cooler heaters, 825 watts
each.
66
15 HP PUMP, 3450 RPM
MCA
MOCP
Rec Fuse
Size
XL
XL
225/175
110/ 90
100/ 80
80/ 60
300/175
150/ 90
125/ 80
100/ 60
300/200
253.2/168.8
300/225
657.5/560.0
150/100
133.5/ 86.4
150/110
351.8/298.4
125/ 90
112.2/ 73.6
125/100
291.8/247.7
100/ 70
90.2/ 59.0
110/ 80
236.5/201.2
350/200
320.3/168.8
400/225
775.6/560.0
200/100
171.1/ 86.4
200/110
430.8/298.4
150/ 90
143.0/ 73.6
175/100
356.5/247.7
125/ 70
116.2/ 59.0
150/ 80
287.8/201.2
350/250
320.3/212.0
400/300
775.6/654.2
200/125
171.1/110.9
200/150
430.8/364.3
150/110
143.0/ 93.6
175/125
356.5/301.6
125/ 90
116.2/ 76.3
150/110
287.8/243.9
350/300
320.3/243.8
400/300
775.6/635.0
200/150
171.1/124.8
200/150
430.8/336.8
150/125
143.0/106.3
175/125
356.5/280.4
125/100
116.2/ 85.2
150/110
287.8/227.4
350/350
332.2/306.2
400/400
787.6/748.4
200/175
177.7/160.2
225/200
437.3/413.6
175/150
148.4/135.2
175/175
361.9/343.2
125/125
120.5/110.2
150/125
292.1/277.8
500/300
438.4/243.8
500/300
893.7/635.0
250/150
233.5/124.8
250/150
493.1/336.8
225/125
195.4/106.3
225/125
408.9/280.4
175/100
158.7/ 85.2
175/110
330.4/227.4
500/350
438.4/306.2
500/400
893.7/748.4
250/175
233.5/160.2
250/200
493.1/413.6
225/150
195.4/135.2
225/175
408.9/343.2
175/125
158.7/110.2
175/125
330.4/277.8
600/300
556.5/243.8
600/300 1011.8/635.0
300/150
295.9/124.8
300/150
555.5/336.8
250/125
247.8/106.3
250/125
461.3/280.4
225/100
201.3/ 85.2
225/110
372.9/227.4
600/350
556.5/306.2
600/400 1011.8/748.4
300/175
295.9/160.2
350/200
555.5/413.6
250/150
247.8/135.2
250/175
461.3/343.2
225/125
201.3/110.2
225/125
372.9/277.8
600/450
580.4/400.4
600/450 1035.7/842.6
350/225
309.0/209.5
350/250
568.6/462.9
300/200
258.6/176.8
300/200
472.1/384.8
225/175
209.9/144.1
225/175
381.5/311.7
208/230
460
575 v only
ICF
Rec Fuse
Size
XL
300/200
150/100
125/ 90
100/ 70
350/200
200/100
175/ 90
125/ 70
350/250
200/125
175/110
125/ 90
350/300
200/150
175/125
125/100
400/350
200/175
175/150
150/125
500/300
250/150
225/125
175/100
500/350
250/175
225/150
175/125
600/300
350/150
300/125
225/100
600/350
350/175
300/150
225/125
600/450
350/225
300/200
225/175