Carrier 30RB060-390 Installation Instructions Manual page 62

Aquasnap air-cooled chillers and / with greenspeed technology
Hide thumbs Also See for 30RB060-390:
Table of Contents

Advertisement

UNIT VOLTAGE
UNIT 30RB
Supplied
V-Hz (3 Ph)
Min
208/230-60
187
380-60
342
060
460-60
414
575-60
518
208/230-60
187
380-60
342
070
460-60
414
575-60
518
208/230-60
187
380-60
342
080
460-60
414
575-60
518
208/230-60
187
380-60
342
090
460-60
414
575-60
518
208/230-60
187
380-60
342
100
460-60
414
575-60
518
208/230-60
187
380-60
342
110
460-60
414
575-60
518
208/230-60
187
380-60
342
120
460-60
414
575-60
518
208/230-60
187
380-60
342
130
460-60
414
575-60
518
208/230-60
187
380-60
342
150
460-60
414
575-60
518
208/230-60
187
380-60
342
160
460-60
414
575-60
518
208/230-60
187
380-60
342
170
460-60
414
575-60
518
208/230-60
187
380-60
342
190
460-60
414
575-60
518
LEGEND
AWG — American Wire Gage
ICF
— Instantaneous Current Flow
MCA — Minimum Circuit Amps
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit
terminals is not below or above the listed minimum and maximum limits. Maximum
allowable phase imbalance is: voltage, 2%; amps 10%.
2. All units or modules have single point primary power connection. (Each unit or module
requires its own power supply.) Main power must be supplied from a field-supplied
disconnect.
3. Cooler heater is wired into the control circuit so it is always operable as long as the
power supply disconnect is on, even if any safety device is open.
4. For MCA that is less than or equal to 380 amps, 3 conductors are required.
For MCA between 381-760 amps, 6 conductors are required.
For MCA between 761-1140 amps, 9 conductors are required.
For MCA between 1141-1520 amps, 12 conductors are required.
Calculation of conductors required is based on 75 C copper wire.
Table 10A — 30RB060-190 Electrical Data — Single Point Units
NO HYDRONIC PACKAGE
MCA
MOCP
Max
XL
XL
253
291.5
350
418
150.9
175
506
127.9
150
633
102.4
125
253
334.7
400
418
175.5
200
506
147.9
175
633
119.8
150
253
366.5
400
418
189.3
225
506
160.6
175
633
128.6
150
253
433.6
500
418
226.9
250
506
191.4
225
633
154.6
175
253
472.0
500
418
248.7
250
506
209.2
250
633
170.0
200
253
508.6
600
418
265.3
300
506
224.1
250
633
180.8
200
253
578.1
600
1020.4
418
304.6
350
506
256.2
300
464.2
633
208.2
225
253
626.7
700
1068.9
418
327.7
350
506
276.5
300
633
223.3
250
253
684.3
700
1126.5
418
360.4
400
506
303.2
350
633
246.4
250
253
744.8
800
1187.0
418
390.1
400
506
328.9
350
633
265.9
300
253
802.4
1000
1244.6
418
422.8
450
506
355.6
400
633
289.0
300
253
920.5
1000
1362.7
418
485.2
500
506
408.0
450
633
331.5
350
MOCP — Maximum Overcurrent Protection
XL
— Across-the-Line Start
3 HP PUMP, 1750 RPM
ICF
MCA
MOCP
Rec Fuse
Size
XL
XL
XL
682.8
350
300.6
350
362.9
175
156.0
175
302.0
150
132.1
150
244.7
110
105.7
125
777.0
400
343.8
400
428.8
200
180.8
225
355.9
175
152.1
175
287.4
150
123.1
150
757.8
400
401.3
200
334.7
175
270.9
150
875.9
500
480.3
250
399.4
225
322.2
175
914.3
500
502.1
250
417.2
225
337.6
200
950.9
600
518.7
300
432.1
250
348.4
200
600
538.0
350
300
325.8
225
700
581.1
350
484.5
300
391.0
250
700
613.8
400
511.2
350
414.1
250
800
643.5
400
536.9
350
433.5
300
1000
676.2
450
563.6
400
456.6
300
1000
738.5
500
616.0
450
499.1
350
5. Wiring for main field supply must be rated 75 C minimum. Use copper for all units.
a. Incoming wire size range for the terminal block is no. 4 AWG to 500 kcmil.
b. Incoming wire size range of non-fused disconnect with MCA up to 599.9 amps is
3/0 to 500 kcmil.
c. Incoming wire size range of non-fused disconnect with MCA from 600 to
799.9 amps is 1/0 to 500 kcmil.
d. Incoming wire size range of non-fused disconnect with MCA from 800 to
1199.9 amps is 250 kcmil to 500 kcmil.
6. Hydronic pump packages are not available as a factory-installed option for units
30RB210-390.
7. Power draw includes both crankcase heaters and cooler heaters (where used). Each
compressor has a crankcase heater which draws 56 watts of power. Units ordered with
the cooler heater option have 1 (060-150) or 2 (160-300) cooler heaters, 825 watts
each.
62
5 HP PUMP, 1750 RPM
ICF
MCA
MOCP
Rec Fuse
Size
XL
XL
XL
693.6
350
306.9
350
368.8
175
159.0
175
306.9
150
135.0
150
248.6
125
107.8
125
787.8
400
350.1
400
434.7
200
183.6
225
360.8
175
155.0
175
291.3
150
125.2
150
381.9
450
197.4
225
167.7
200
134.0
150
449.0
500
235.0
250
198.5
225
160.0
175
487.4
500
256.8
300
216.3
250
175.4
200
524.0
600
273.4
300
231.2
250
186.2
200
593.5
600
312.7
350
263.3
300
213.6
225
642.1
700
335.8
350
283.6
300
228.7
250
699.7
700
368.5
400
310.3
350
251.8
300
760.2
800
398.2
400
336.0
350
271.3
300
817.8
1000
430.9
450
362.7
400
294.4
300
935.9
1000
493.3
500
415.1
450
336.9
350
208/230
460
575 v only
ICF
Rec Fuse
Size
XL
700.5
350
372.6
175
310.0
150
251.1
125
794.7
400
438.5
200
363.9
175
293.8
150
775.5
450
411.0
225
342.7
200
277.3
150
893.6
500
490.0
250
407.4
225
328.6
175
932.0
500
511.8
300
425.2
250
344.0
200
968.6
600
528.4
300
440.1
250
354.8
200
1038.1
700
567.6
350
472.2
300
382.2
225
1086.6
700
590.8
350
492.5
300
397.4
250
1144.2
800
623.5
400
519.2
350
420.5
300
1204.7
800
653.2
400
544.9
350
439.9
300
1262.3
1000
685.9
450
571.6
400
463.0
300
1380.4
1000
748.2
500
624.0
450
505.5
350