Carrier AquaSnap 30RC010 Installation Instructions Manual
Carrier AquaSnap 30RC010 Installation Instructions Manual

Carrier AquaSnap 30RC010 Installation Instructions Manual

Air-cooled chillers with greenspeed technology

Advertisement

Quick Links

CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Storage Recommendations . . . . . . . . . . . . . . . . . . . . 2
Step 1 - Place and Rig the Unit . . . . . . . . . . . . . . . . 3
Step 4 - Fill the Chilled Water Loop . . . . . . . . . . . 29
Step 6 - Install Accessories . . . . . . . . . . . . . . . . . . 48
Step 7 - Check Refrigerant Circuit . . . . . . . . . . . . 48
COMMUNICATION BUS WIRING
APPENDIX A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300247-01
Installation Instructions
Page
®
Printed in U.S.A.
Form No. 30RC-100SI
30RC010-060 Air-Cooled Chillers
with Greenspeed Technology

SAFETY CONSIDERATIONS

Installing, starting up, and servicing air-conditioning equipment
can be hazardous due to system pressures, electrical components,
and equipment location.
Only trained, qualified installers and service mechanics should
install, start up, and service this equipment.
Untrained personnel can perform basic maintenance functions,
such as cleaning coils. All other operations should be performed
by trained service personnel. Qualified installers and service tech-
nicians are required to have been trained on the following topics
when installing and servicing air-conditioning equipment with
A2L refrigerant such as R-32:
1.
Explosive potential of A2L refrigerants
2.
Potential ignition sources
3.
Safety measures for unventilated and ventilated rooms or
enclosures
4.
Refrigerant detectors
5.
Concept of sealed components and sealed enclosures
according to IEC 60079-15:2010
6.
Correct work procedures for the following:
a. Commissioning
b. Maintenance
c. Repair
d. Decommissioning
e. Disposal
Refer to Controls and Troubleshooting Guide for complete guide-
lines. When working on the equipment, observe precautions in the
literature and on tags, stickers, and labels attached to the
equipment.
1.
Follow all safety codes.
2.
Keep quenching cloth and fire extinguisher nearby when
brazing.
3.
Wear safety glasses and work gloves.
4.
Use care in handling, rigging, and setting bulky equipment.
It is important to recognize safety information. This is the safety-
alert symbol
. When you see this symbol on the unit and in in-
structions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION,
and NOTE. These words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies hazards
which could result in personal injury or death. CAUTION is used
to identify unsafe practices, which may result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability,
or operation.
Pg 1
AquaSnap
2-24
Replaces: NEW
®

Advertisement

Table of Contents
loading

Summary of Contents for Carrier AquaSnap 30RC010

  • Page 1: Table Of Contents

    Wear safety glasses and work gloves. • CHARGING PROCEDURES Use care in handling, rigging, and setting bulky equipment. • RECOVERY • CARRIER COMFORT NETWORK ® (CCN) It is important to recognize safety information. This is the safety- COMMUNICATION BUS WIRING alert symbol .
  • Page 2: Installation

    NOTE: Take notice of the following symbols, which are required for A2L refrigerants and can be found on the unit: WARNING SYMBOL CODE MEANING DO NOT USE TORCH to remove any component. System contains oil and refrigerant under pressure. IEC 60417-5032 (2002-10) Alternating current To remove a component, wear protective gloves and goggles and proceed as follows:...
  • Page 3: Inspection During Storage

    Carrier 3.5 ft (1.1 m) recommends one of the following steps be taken to ensure no cor- MINIMUM† rosion occurs: Install blank-off Victualic™ plates on the chilled water con- nections. Completely fill the chilled water piping with an 6 ft (1.8 m)
  • Page 4 30RC 30RC – Air-Cooled AquaSnap Chiller Packaging Options 0 – Coil Face Shipping Protection (CFSP) 1 – Skid Only (CFSP) Design Series 2 – Hail Guards, Skid + Bag 3 – Hail Guards Only Unit Sizes 4 – Skid + Bag (CFSP) 010 030 050 015 035 055 Controls / Communications Options...
  • Page 5 Table 1 — MCHX Coil, No Pump Units POUNDS KILOGRAMS 30RC 30RC SIZE SIZE Total Weight Total Weight 1305 1445 1478 2309 1047 2335 1059 2417 1096 2438 1106 2543 1153 2646 1200 Table 2 — MCHX Coil, Single Pump Units POUNDS KILOGRAMS 30RC...
  • Page 6 Table 4 — AL/CU Coil, No Pump Units POUNDS KILOGRAMS 30RC 30RC SIZE SIZE Total Weight Total Weight 1041 1377 1377 1535 1567 2454 1113 2480 1125 2596 1177 2616 1187 1187 2722 1235 2825 1281 Table 5 — AL/CU Coil, Single Pump Units POUNDS KILOGRAMS 30RC...
  • Page 7 Table 7 — Physical Data, 30RC 010-025 — English UNIT 30RC CHASSIS DIMENSIONS (in.) Length Width Height SHIPPING WEIGHT (lb) MCHX Condenser, No Pump 1271 1400 MCHX Condenser, Single Pump 1077 1117 1434 1563 MCHX Condenser, Dual Pump 1239 1280 1596 1597 Al-Cu Condenser, No Pump...
  • Page 8 Table 7 — Physical Data, 30RC 010-025 — English (cont) UNIT 30RC CONDENSER FANS Axial Vertical Discharge, Composite Fan Speed (rpm) No. Blades...Diameter (in.) 9...30 No. Fans Total Airflow (cfm) 9,400 9,400 17,500 19,400 CONDENSER COILS Novation MCHX Aluminum Tube, Aluminum Fin (Optional Round Tube Plate Fin Quantity (Ckt A/Ckt B) Total Face Area (sq ft) Maximum Refrigerant Pressure (psig)
  • Page 9 Table 8 — Physical Data, 30RC 030-060 — English UNIT 30RC CHASSIS DIMENSIONS (in.) Length Width Height SHIPPING WEIGHT (lb) 2237 2255 2337 2356 2458 2561 MCHX Condenser, No Pump 1434 2581 2599 2681 2699 2802 2805 MCHX Condenser, Single Pump 1597 2924 2942...
  • Page 10 Table 8 — Physical Data, 30RC 030-060 — English (cont) UNIT 30RC CONDENSER FANS Axial Vertical Discharge, Composite Fan Speed (rpm) No. Blades...Diameter (in.) 9...30 No. Fans Total Airflow (cfm) 19,400 29,600 30,500 30,500 30,500 38,800 38,500 CONDENSER COILS Novation MCHX Aluminum Tube, Aluminum Fin (Optional Round Tube Plate Fin Quantity (Ckt A/Ckt B) Total Face Area (sq ft) Maximum Refrigerant Pressure (psig)
  • Page 11 Table 9 — Physical Data, 30RC 010-025 — SI UNIT 30RC CHASSIS DIMENSIONS (mm) Length 1117 1117 2260 2260 Width 1701 1701 1701 1701 Height 1701 1701 1701 2006 SHIPPING WEIGHT (kg) MCHX Condenser, No Pump MCHX Condenser, Single Pump MCHX Condenser, Dual Pump Al-Cu Condenser, No Pump Al-Cu Condenser, Single Pump...
  • Page 12 Table 9 — Physical Data, 30RC 010-025 — SI (cont) UNIT 30RC CONDENSER FANS Axial Vertical Discharge, Composite Fan Speed (rpm) No. Blades...Diameter (mm) 9...762 No. Fans Total Airflow (cfm) 9,400 9,400 17,500 19,400 CONDENSER COILS Novation MCHX Aluminum Tube, Aluminum Fin (Optional Round Tube Plate Fin Quantity (Ckt A/Ckt B) Total Face Area (sq m) 1.76...
  • Page 13 Table 10 — Physical Data, 30RC 030-060 — SI (cont) UNIT 30RC CHASSIS DIMENSIONS (mm) Length 2260 2260 2260 2260 2260 2260 2260 Width 1701 2438 2438 2438 2438 2438 2438 Height 1701 1701 1701 2006 2006 2006 2006 SHIPPING WEIGHT (kg) MCHX Condenser, No Pump 1015 1023...
  • Page 14 Table 10 — Physical Data, 30RC 030-060 — SI (cont) UNIT 30RC CONDENSER FANS Axial Vertical Discharge, Composite Fan Speed (rpm) No. Blades...Diameter (mm) 9...762 No. Fans Total Airflow (cfm) 19,400 29,600 30,500 30,500 30,500 38,800 38,500 CONDENSER COILS Novation MCHX Aluminum Tube, Aluminum Fin (Optional Round Tube Plate Fin Quantity (Ckt A/Ckt B) Total Face Area (sq m) Maximum Refrigerant Pressure (kPa)
  • Page 15 Fig. 4 — Unit Rigging Label Detail...
  • Page 16: Mounting Unit

    Failure to use the strainer represents abuse and may impair or must not be turned off except when unit is being serviced. otherwise negatively affect the Carrier product warranty. Installation of water systems should follow sound engineering practice as well as applicable local and industry standards. Im-...
  • Page 17 Fig. 5 — Dimensions — 30RC010 and 015 Units...
  • Page 18 Fig. 6 — Dimensions — 30RC020-030 Units...
  • Page 19 Fig. 7 — Dimensions — 30RC035-050 Units...
  • Page 20 Fig. 8 — Dimensions — 30RC055-060 Units...
  • Page 21 Ø7/16" [11] X 1" [25] LG SLOT SEE DETAIL A 2 X 1" [25] DETAIL A Ø2-1/2 IN. VICTAULIC WATER 1' 5-13/32" AT (4) PLCS INLET/OUTLET [442] 1' 1/32" [306] TANK ACCESS .88" [22.35]Ø KNOCKOUT 1' 11-1/2" [597] TANK TANK FOR POWER TO CONTROL BOX CENTER OF GRAVITY TANK...
  • Page 22 Ø7/32" [6] X 1" [25] LG SLOT SEE DETAIL A 2 X 1" [25] DETAIL A 1' 5-13/32" Ø.88" (22.35) KNOCKOUT FOR Ø2-1/2" VICTAULIC WATER AT (4) PLCS [442] POWER TO THE CONTROL BOX INLET/OUTLET 1' 1/32" TANK [305] ACCESS TANK TANK ACCESS...
  • Page 23 3" [76.2] Ø7/32" [6] X 1" [25] LG SLOT MOUNTING HOLES, FOUR CORNERS (TYP) SEE DETAIL A Ø.395/.405 (TYP) 1-1/2" 1' 5-13/32" MOUNTING HOLES, [38.1] MIDDLE EACH SIDE [442] DETAIL A AT (4) PLCS 1' [305] TANK TANK 3' 7-31/32" ACCESS ACCESS Ø.88"...
  • Page 24 ® tween the two chillers. For more information regarding Communi- If the dual chiller algorithm is utilized the machines must be in- cation Bus Wiring, see the Carrier Comfort Network (CCN) In- ® stalled in parallel. An additional chilled water sensor must be in- terface section of the Controls, Start-Up, Operation, Service, and stalled.
  • Page 25: Victaulic Coupling Installation

    VICTAULIC COUPLING INSTALLATION UNITS WITH FACTORY-INSTALLED HYDRONIC PACKAGES The outside surface of the pipe, between the groove and the pipe end, must be smooth and free from indentations, projec- The 30RC chillers with factory-installed hydronic packages are tions (including weld seams), and roll marks to ensure a leak- designed for use with closed systems, meaning that there is no tight seal.
  • Page 26 LEGEND Factory Supplied Strainer/Blow-Down Valve Flow Switch 1 — 8 — Expansion Tank (011-060 sizes only) Balance Valve/Drain Plug 2 — 9 — Pump Pressure Relief 3 — 10 — Electric Heater Isolation Valves 4 — 11 — Air Vent Connection Port Flex Connections 5 —...
  • Page 27 LEGEND 1 — Strainer (40 Mesh) 8 — Flow Switch 4 — Electric Heater 10 — Pressure Relief 5 — Air Vent Connection Port 11 — Isolation Valves 6 — Pressure/Temperature Access Port 12 — Flex Connections 7 — Heat Exchanger 13 —...
  • Page 28: Air Separation

    The compression tank pressure must be set BEFORE the system is This is also true for applications where two or more 30RC chillers filled. Expansion tanks are factory supplied. The tanks are pre- are placed in parallel. There should not be more than one expan- charged at the factory to 40 psig (276 kPa).
  • Page 29: Step 4 - Fill The Chilled Water Loop

    Water quality should be maintained within the limits indicated in age outside the unit. Table 12. Failure to maintain proper water quality may result in Carrier’s PIC6 controls have a built-in feature to remind building heat exchanger failure. owners or operators to clean the strainer by discharging the blow- down valve at a pre-set time interval.
  • Page 30: Filling The System

    The gpm corresponding to the pressure drop measured is the Fig. 19 — Typical Set Up for Cleaning Process flow through the balancing valve. NOTE: Carrier recommends a differential pressure gage when SYSTEM measuring pressures across the pumps or balancing valves. This...
  • Page 31 Table 13 — Balancing Valve Readings — 30RC010-030 WATER PRESSURE DROP (ft) VALVE 2.0 in. COEFFICIENT SETTING 13.4 21.0 30.2 41.1 53.7 67.9 83.8 10.2 13.9 20.0 27.2 35.5 45.0 55.5 13.0 12.3 16.7 21.9 27.7 34.2 16.9 12.9 16.4 20.2 20.5 11.1...
  • Page 32 Table 15 — Glycol Correction Factors GLYCOL CORRECTION FACTOR Ethylene Propylene CONCENTRATION Water Temp —°F (°C) 40 (4.5) 70 (21) 40 (4.5) 70 (21) 1.00 1.00 1.00 1.00 0.99 0.99 0.99 0.99 0.99 0.99 0.99 0.99 0.98 0.98 0.99 0.99 0.97 0.97 0.98...
  • Page 33 50.00 45.00 40.00 35.00 30.00 25.00 20.00 15.00 10.00 5.00 0.00 LEGEND 6 - 30RC035 7 - 30RC040,045 8 - 30RC050 9 - 30RC055,060 Fig. 22 — Heat Exchanger Pressure Drop (Water Only) — 30RC035-060 (English) LITERS/SECOND LEGEND 1 - 30RC010 2 - 30RC015 3 - 30RC020 4 - 30RC025,030...
  • Page 34 LITER/SECOND LEGEND 5 - 30RC035 6 - 30RC040,045 7 - 30RC050 8 - 30RC055,060 Fig. 24 — Heat Exchanger Pressure Drop (Water Only) — 30RC035-060 (SI) Minimum Loop Volume The minimum volume of fluid required to be in circulation is a function of the number of compressors in the chiller as well as the type of application.
  • Page 35: Preparation For Year-Round Operation

    NOTE: Do not use automobile antifreeze, or any other fluid be done by a qualified machine shop that has experience in this that is not approved for heat exchanger duty. Use only operation. Contact your local Carrier representative for a...
  • Page 36: Preparation For Winter Shutdown

    Ensure that power is available to the chiller at all times, even affect Carrier warranty. during the off-season, so that the pump and evaporator heat- ers have power. Also make sure that the piping tape heaters POWER WIRING have power.
  • Page 37 Table 20 — 30RC Single Point Power - Standard Compressor UNIT VOLTAGE NO HYDRONIC PACKAGE UNIT NO. OF Supplied REC FUSE 30RC COND FANS V(3 Ph) MOCP SIZE 208/230 51.7 29.0 26.9 19.2 208/230 70.2 42.4 34.6 25.5 208/230 95.7 54.1 45.0 34.2...
  • Page 38 Table 20 — 30RC Single Point Power - Standard Compressor (cont) UNIT SINGLE 1.5 HP PUMP, 3600 RPM SINGLE 3.0HP PUMP, 3600 RPM SINGLE 5.0HP PUMP, 3600 RPM VOLTAGE UNIT 30RC V(3 Ph) MOCP FUSE MOCP FUSE MOCP FUSE SIZE SIZE SIZE 208/230...
  • Page 39 Table 20 — 30RC Single Point Power - Standard Compressor (cont) UNIT SINGLE 7.5 HP PUMP, 3600 RPM SINGLE 10 HP PUMP, 3600 RPM VOLTAGE UNIT 30RC REC FUSE REC FUSE V(3 Ph) MOCP MOCP SIZE SIZE 208/230 — — —...
  • Page 40 Table 21 — 30RC Single Point Power - Digital Compressor UNIT VOLTAGE NO HYDRONIC PACKAGE NUMBER UNIT 30RC Supplied OF COND REC FUSE V(3 Ph) MOCP FANS SIZE 208/230 54.2 29.1 26.9 18.8 208/230 69.9 40.3 35.0 25.3 208/230 93.7 54.7 45.9 35.3...
  • Page 41 Table 21 — 30RC Single Point Power - Digital Compressor (cont) UNIT SINGLE 1.5 HP PUMP, 3600 RPM SINGLE 3.0 HP PUMP, 3600 RPM SINGLE 5.0 HP PUMP, 3600 RPM VOLTAGE UNIT 30RC V(3 Ph) MOCP FUSE MOCP FUSE MOCP FUSE SIZE SIZE...
  • Page 42 Table 21 — 30RC Single Point Power - Digital Compressor (cont) UNIT SINGLE 7.5 HP PUMP, 3600 RPM SINGLE 10 HP PUMP, 3600 RPM VOLTAGE UNIT 30RC REC FUSE V(3 Ph) MOCP MOCP FUSE SIZE SIZE 208/230 — — — —...
  • Page 43 Table 22 — Fan Electrical Data — Single Point, Standard Low-Sound Aeroacoustic™ Fans Unit Sizes 010-060 SINGLE POINT Fixed Speed Condenser Greenspeed ECM Condenser Fans UNIT UNIT VOLTAGE Condenser Fans FLA 30RC V-Hz (3 Ph) Fans FLA — 208/230-60 380-60 —...
  • Page 44 Table 23 — Pump Electrical Data (60 Hz Only) 30RC SIZE PUMP OPTION PUMP SIZE PUMP RPM UNIT VOLTAGE V-Hz (3 Ph) FLA (each) 3500 208/230-60 3500 380-60 2, 9 1.5 HP 3500 460-60 3500 575-60 3500 208/230-60 3500 380-60 3, 4, B, C 3.0 HP 3500...
  • Page 45 Table 25 — Compressor Electrical Data Compressors UNIT V(3 Ph) 30RC 208/230 21.7 166.2 15.4 155.0 — — — — — — 11.4 93.9 78.9 — — — — — — 11.7 75.0 58.1 — — — — — — 54.0 47.8 —...
  • Page 46 Table 26 — Digital Compressor Electrical Data Compressors UNIT V(3 Ph) 30RC 208/230 23.7 164.0 15.4 155.0 — — — — — — 11.5 73.0 78.9 — — — — — — 11.7 75.0 58.1 — — — — — —...
  • Page 47 Fig. 26 — Typical Main Power and Control Connections...
  • Page 48: Control Power

    If hot gas bypass accessory is required, refer to unit Price Pages or appropriate purging gas. The system shall be leak-tested on com- contact your local Carrier representative for more details. For in- pletion of charging but prior to commissioning. A follow up leak stallation details, refer to separate installation instructions supplied test shall be carried out prior to leaving the site.
  • Page 49 Hoses shall be complete with leak-free Carrier warranty. disconnect couplings and in good condition. Before using the recovery machine, check that it is in satisfactory...
  • Page 50: Carrier Comfort Network ® (Ccn)

    CARRIER COMFORT NETWORK (CCN) COMMUNICATION communication bus cable exits from one building and enters ® another, the shields must be connected to grounds at the lightning BUS WIRING suppressor in each building where the cable enters or exits the The communication bus wiring is a shielded, 3-conductor cable building (one point per building only).
  • Page 51 — Outside Diameter — Tinned Copper — Underwriters Laboratories (+) (COM) (-) SHIELD (+) (COM) (-) SHIELD (+) (COM) (-) SHIELD SHIELD TO NEXT DEVICE LEGEND — Carrier Comfort Network — Local Equipment Network Fig. 28 — TB-3 — CCN Wiring...
  • Page 52 APPENDIX A Unit Pressure Drop Curves, 30RC010-060 (English) 50.00 45.00 40.00 35.00 30.00 25.00 20.00 15.00 10.00 5.00 0.00 LEGEND 1 - 30RC010 2 - 30RC015 3 - 30RC020 4 - 30RC025,030 70.00 60.00 50.00 40.00 30.00 20.00 10.00 0.00 LEGEND 6 - 30RC035 7 - 30RC040,045...
  • Page 53 APPENDIX A (cont) Unit Pressure Drop Curves, 30RC010-060 (SI) 150.00 125.00 100.00 75.00 50.00 25.00 0.00 LITERS/SECOND LEGEND 1 - 30RC010 2 - 30RC015 3 - 30RC020 4 - 30RC025,030 250.00 225.00 200.00 175.00 150.00 125.00 100.00 75.00 50.00 25.00 0.00 LITER/SECOND LEGEND...
  • Page 54 APPENDIX A (cont) Unit Pressure Drop Curves, 30RC010-060 (English) 50.00 45.00 40.00 35.00 30.00 25.00 20.00 15.00 10.00 5.00 0.00 LEGEND 1 - 30RC010 2 - 30RC015 3 - 30RC020 4 - 30RC025,030 7 8 9 70.00 60.00 50.00 40.00 30.00 20.00 10.00...
  • Page 55 APPENDIX A (cont) Unit Pressure Drop Curves, 30RC010-060 (SI) 150.00 125.00 100.00 75.00 50.00 25.00 0.00 LITERS/SECOND LEGEND 1 - 30RC010 2 - 30RC015 3 - 30RC020 4 - 30RC025,030 6 7 8 250.00 225.00 200.00 175.00 150.00 125.00 100.00 75.00 50.00 25.00...
  • Page 56 APPENDIX A (cont) Unit Pressure Drop Curves, 30RC010-060 (English) 50.00 45.00 40.00 35.00 30.00 25.00 20.00 15.00 10.00 5.00 0.00 LEGEND 1 - 30RC010 2 - 30RC015 3 - 30RC020 4 - 30RC025,030 70.00 60.00 50.00 40.00 30.00 20.00 10.00 0.00 LEGEND 6 - 30RC035...
  • Page 57 APPENDIX A (cont) Unit Pressure Drop Curves, 30RC010-060 (SI) 150.00 125.00 100.00 75.00 50.00 25.00 0.00 LITERS/SECOND LEGEND 1 - 30RC010 2 - 30RC015 3 - 30RC020 4 - 30RC025,030 6 7 8 250.00 225.00 200.00 175.00 150.00 125.00 100.00 75.00 50.00 25.00...
  • Page 58 APPENDIX A (cont) 100.0 30RC035-060 10.0 30RC010-030 1000 ACCESSORY TANK FLOW RATE (gpm) 100.0 30RC035-060 10.0 30RC010-030 10.0 ACCESSORY TANK FLOW RATE (L/s) Fig. D — Pressure Drop Curves, Accessory Storage Tanks...
  • Page 60 © 2024 Carrier Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53300247-01 Printed in U.S.A. Form No. 30RC-100SI Pg 60 2-24 Replaces: NEW...

Table of Contents