Carrier 30RB060-390 Installation Instructions Manual page 65

Aquasnap air-cooled chillers and / with greenspeed technology
Hide thumbs Also See for 30RB060-390:
Table of Contents

Advertisement

UNIT VOLTAGE
30RB
Supplied
UNIT
V-Hz
SIZE
(3 Ph)
Min
Max
208/230-60
187
253
168.8/141.5
380-60
342
418
86.4/ 74.1
060
460-60
414
506
73.6/ 62.5
575-60
518
633
59.0/ 50.0
208/230-60
187
253
212.0/141.5
380-60
342
418
110.9/ 74.1
070
460-60
414
506
93.6/ 62.5
575-60
518
633
76.3/ 50.0
208/230-60
187
253
216.5/168.8
380-60
342
418
112.5/ 86.4
080
460-60
414
506
95.2/ 73.6
575-60
518
633
76.2/ 59.0
208/230-60
187
253
283.6/168.8
380-60
342
418
150.1/ 86.4
090
460-60
414
506
126.0/ 73.6
575-60
518
633
102.2/ 59.0
208/230-60
187
253
283.6/212.0
380-60
342
418
150.1/110.9
100
460-60
414
506
126.0/ 93.6
575-60
518
633
102.2/ 76.3
208/230-60
187
253
283.6/243.8
380-60
342
418
150.1/124.8
110
460-60
414
506
126.0/106.3
575-60
518
633
102.2/ 85.2
208/230-60
187
253
295.5/306.2
380-60
342
418
156.7/160.2
120
460-60
414
506
131.4/135.2
575-60
518
633
106.5/110.2
208/230-60
187
253
401.7/243.8
380-60
342
418
212.5/124.8
130
460-60
414
506
178.4/106.3
575-60
518
633
144.7/ 85.2
208/230-60
187
253
401.7/306.2
380-60
342
418
212.5/160.2
150
460-60
414
506
178.4/135.2
575-60
518
633
144.7/110.2
208/230-60
187
253
519.8/243.8
380-60
342
418
274.9/124.8
160
460-60
414
506
230.8/106.3
575-60
518
633
187.3/ 85.2
208/230-60
187
253
519.8/306.2
380-60
342
418
274.9/160.2
170
460-60
414
506
230.8/135.2
575-60
518
633
187.3/110.2
208/230-60
187
253
543.7/400.4
380-60
342
418
288.0/209.5
190
460-60
414
506
241.6/176.8
575-60
518
633
195.9/144.1
LEGEND
AWG
— American Wire Gage
ICF
— Instantaneous Current Flow (Ckt1/Ckt2)
MCA
— Minimum Circuit Amps (Ckt1/Ckt2)
MOCP — Maximum Overcurrent Protection (Ckt1/Ckt2)
XL
— Across-the-Line Start
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit
terminals is not below or above the listed minimum and maximum limits. Maximum
allowable phase imbalance is: voltage, 2%; amps 10%.
2. Control power is derived from main power. No separate control power connection is
required.
3. Cooler heater is wired into the control circuit so it is always operable as long as the
power supply disconnect is on, even if any safety device is open.
4. For MCA that is less than or equal to 380 amps, 3 conductors are required.
For MCA between 381-760 amps, 6 conductors are required.
For MCA between 761-1140 amps, 9 conductors are required.
For MCA between 1141-1520 amps, 12 conductors are required.
Calculation of conductors required is based on 75 C copper wire.
Table 11A — 30RB060-190 Electrical Data — Dual Point Units
NO HYDRONIC PACKAGE
MCA
MOCP
ICF
XL
XL
XL
225/200
560.0/532.8
200/175
110/110
298.4/286.1
100/ 90
100/ 90
247.7/236.6
80/ 70
201.2/192.3
300/200
654.2/532.8
250/175
150/110
364.3/286.1
125/ 90
125/ 90
301.6/236.6
110/ 80
110/ 70
243.9/192.3
250/225
607.8/560.0
250/200
150/110
324.5/298.4
125/100
125/100
269.3/247.7
110/ 90
100/ 80
218.5/201.2
350/225
725.9/560.0
350/200
175/110
403.5/298.4
175/100
150/100
334.0/247.7
150/ 90
125/ 80
269.8/201.2
125/ 70
350/300
725.9/654.2
350/250
175/150
403.5/364.3
175/125
150/125
334.0/301.6
150/110
125/110
269.8/243.9
125/ 90
350/300
725.9/635.0
350/300
175/150
403.5/336.8
175/150
150/125
334.0/280.4
150/125
125/110
269.8/227.4
125/100
350/400
737.8/748.4
350/350
200/200
410.1/413.6
175/175
150/175
339.4/343.2
150/150
125/125
274.1/277.8
125/125
450/300
843.9/635.0
450/300
250/150
465.9/336.8
225/150
200/125
386.4/280.4
200/125
175/110
312.4/227.4
175/100
450/400
843.9/748.4
450/350
250/200
465.9/413.6
225/175
200/175
386.4/343.2
200/150
175/125
312.4/277.8
175/125
600/300
962.0/635.0
600/300
300/150
528.3/336.8
300/150
250/125
438.8/280.4
250/125
200/110
354.9/227.4
200/100
600/400
962.0/748.4
600/350
300/200
528.3/413.6
300/175
250/175
438.8/343.2
250/150
200/125
354.9/277.8
200/125
600/450
985.9/842.6
600/450
300/250
541.3/462.9
300/225
250/200
449.6/384.8
250/200
225/175
363.5/311.7
225/175
3 HP PUMP, 1750 RPM
Rec
MCA
MOCP
ICF
Fuse
XL
XL
XL
Size
177.9/141.5
250/200
570.8/532.8
91.5/ 74.1
125/110
304.3/286.1
90/ 80
77.8/ 62.5
110/ 90
252.6/236.6
70/ 60
62.3/ 50.0
80/ 70
205.1/192.3
221.1/141.5
300/200
665.0/532.8
116.0/ 74.1
150/110
370.2/286.1
97.8/ 62.5
125/ 90
306.5/236.6
90/ 60
79.6/ 50.0
110/ 70
247.8/192.3
90/ 70
5. Wiring for main field supply must be rated 75 C minimum. Use copper for all units.
a. Incoming wire size range for the terminal block is no.4 AWG to 500 kcmil.
b. Incoming wire size range of non-fused disconnect with MCA up to 599.9 amps is
3/0 to 500 kcmil.
c. Incoming wire size range of non-fused disconnect with MCA from 600 to
799.9 amps is 1/0 to 500 kcmil.
d. Incoming wire size range of non-fused disconnect with MCA from 800 to
1199.9 amps is 250 kcmil to 500 kcmil.
6. Hydronic pump packages are not available as a factory-installed option for units
30RB210-390.
7. Power draw includes both crankcase heaters and cooler heaters (where used). Each
compressor has a crankcase heater which draws 56 watts of power. Units ordered with
the cooler heater option have 1 (060-150) or 2 (160-300) cooler heaters, 825 watts
each.
65
5 HP PUMP, 1750 RPM
Rec
MCA
MOCP
ICF
Fuse
XL
XL
Size
200/175
184.2/141.5
250/200
577.7/532.8
110/ 90
94.5/ 74.1
125/110
308.1/286.1
90/ 80
80.7/ 62.5
110/ 90
255.7/236.6
70/ 60
64.4/ 50.0
90/ 70
207.6/192.3
250/175
227.4/141.5
300/200
671.9/532.8
150/ 90
119.0/ 74.1
150/110
374.0/286.1
110/ 80
100.7/ 62.5
125/ 90
309.6/236.6
90/ 60
81.7/ 50.0
110/ 70
250.3/192.3
231.9/168.8
300/225
625.5/560.0
120.6/ 86.4
150/110
334.2/298.4
102.3/ 73.6
125/100
277.3/247.7
81.6/ 59.0
100/ 80
224.9/201.2
299.0/168.8
350/225
743.5/560.0
158.2/ 86.4
200/110
413.2/298.4
133.1/ 73.6
150/100
342.0/247.7
107.6/ 59.0
125/ 80
276.2/201.2
299.0/212.0
350/300
743.5/654.2
158.2/110.9
200/150
413.2/364.3
133.1/ 93.6
150/125
342.0/301.6
107.6/ 76.3
125/110
276.2/243.9
299.0/243.8
350/300
743.5/635.0
158.2/124.8
200/150
413.2/336.8
133.1/106.3
150/125
342.0/280.4
107.6/ 85.2
125/110
276.2/227.4
310.9/306.2
400/400
755.5/748.4
164.8/160.2
200/200
419.7/413.6
138.5/135.2
175/175
347.4/343.2
111.9/110.2
125/125
280.5/277.8
417.1/243.8
500/300
861.6/635.0
220.6/124.8
250/150
475.6/336.8
185.5/106.3
225/125
394.4/280.4
150.1/ 85.2
175/110
318.8/227.4
417.1/306.2
500/400
861.6/748.4
220.6/160.2
250/200
475.6/413.6
185.5/135.2
225/175
394.4/343.2
150.1/110.2
175/125
318.8/277.8
535.2/243.8
600/300
979.7/635.0
283.0/124.8
300/150
538.0/336.8
237.9/106.3
250/125
446.8/280.4
192.7/ 85.2
225/110
361.3/227.4
535.2/306.2
600/400
979.7/748.4
283.0/160.2
300/200
538.0/413.6
237.9/135.2
250/175
446.8/343.2
192.7/110.2
225/125
361.3/277.8
559.1/400.4
600/450
1003.6/842.6
296.1/209.5
300/250
551.0/462.9
248.7/176.8
250/200
457.6/384.8
201.3/144.1
225/175
369.9/311.7
208/230
460
575 v only
Rec
Fuse
XL
Size
225/175
110/ 90
90/ 80
80/ 60
300/175
150/ 90
125/ 80
100/ 60
300/200
150/100
125/ 90
90/ 70
350/200
175/100
150/ 90
125/ 70
350/250
175/125
150/110
125/ 90
350/300
175/150
150/125
125/100
350/350
200/175
150/150
125/125
450/300
250/150
200/125
175/100
450/350
250/175
200/150
175/125
600/300
300/150
250/125
225/100
600/350
300/175
250/150
225/125
600/450
300/225
250/200
225/175