ControlWave Instruction Manual (CI-ControlWave)
Software Configuration To use data from an Isolated Low Level Analog Input module you
3-44
Thermocouple
Type
C
N
J
E
K
T
Note: Use straight-line approximation to calculate approximate error between
end points.
must add a CW_TC12 board in ControlWave Designer's I/O
Configurator, and then configure it. See the ControlWave Designer
Programmer's Handbook (D5125) for more information. That same
manual includes an I/O Mapping section that describes, for advanced
users, the I/O map for this module.
I/O Modules
Process Temperature
Range
0C to 2315C
– 270C to – 261C
– 260C to – 251C
– 250C to – 231C
– 230C to – 189C
– 188C to – 70C
– 70C to + 25C
+25C to 1300C
– 210C to – 111C
– 110C to +25C
+25C to 1200C
– 270C to – 261C
– 260C to – 245C
– 244C to – 200C
– 200C to – 87C
– 86C to +25C
+25C to 100C
– 270C to – 261C
– 260C to – 247C
– 246C to – 222C
– 220C to – 160C
– 159C to +25C
+25C to 1372C
– 270C to – 261C
– 260C to – 243C
– 242C to – 196C
– 195C to – 61C
– 60C to +25C
+25C to 400C
RTD Error with CJC
@ 25C
0.30C
20.50C
5.00C
2.70C
1.40C
0.70C
0.35C
0.30C
0.80C
0.40C
0.30C
10C
3C
1.50C
0.75C
0.39C
0.30C
15.00C
4.50C
2.20C
1.10C
0.55C
0.30C
10.30C
3.00C
1.50C
0.75C
0.375C
0.30C
Revised Nov-2010