Emerson ControlWave Instruction Manual page 92

Process automation controller
Hide thumbs Also See for ControlWave:
Table of Contents

Advertisement

ControlWave Instruction Manual (CI-ControlWave)
Software Configuration To use data from an Isolated Low Level Analog Input module you
3-44
Thermocouple
Type
C
N
J
E
K
T
Note: Use straight-line approximation to calculate approximate error between
end points.
must add a CW_TC12 board in ControlWave Designer's I/O
Configurator, and then configure it. See the ControlWave Designer
Programmer's Handbook (D5125) for more information. That same
manual includes an I/O Mapping section that describes, for advanced
users, the I/O map for this module.
I/O Modules
Process Temperature
Range
0C to 2315C
– 270C to – 261C
– 260C to – 251C
– 250C to – 231C
– 230C to – 189C
– 188C to – 70C
– 70C to + 25C
+25C to 1300C
– 210C to – 111C
– 110C to +25C
+25C to 1200C
– 270C to – 261C
– 260C to – 245C
– 244C to – 200C
– 200C to – 87C
– 86C to +25C
+25C to 100C
– 270C to – 261C
– 260C to – 247C
– 246C to – 222C
– 220C to – 160C
– 159C to +25C
+25C to 1372C
– 270C to – 261C
– 260C to – 243C
– 242C to – 196C
– 195C to – 61C
– 60C to +25C
+25C to 400C
RTD Error with CJC
@ 25C
 0.30C
 20.50C
 5.00C
 2.70C
 1.40C
 0.70C
 0.35C
 0.30C
 0.80C
 0.40C
 0.30C
 10C
 3C
 1.50C
 0.75C
 0.39C
 0.30C
 15.00C
 4.50C
 2.20C
 1.10C
 0.55C
 0.30C
 10.30C
 3.00C
 1.50C
 0.75C
 0.375C
 0.30C
Revised Nov-2010

Hide quick links:

Advertisement

Table of Contents
loading