CASH VALVE™ TYPE B ¼" TO 2" FOR CRYOGENIC SERVICE
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
Before installation, these instructions must be carefully read and understood.
WARNING
Failure to follow these instructions or to properly
install and maintain this equipment could result in
an explosion, fire and/or chemical contamination
causing property damage and personal injury
or death.
Cash Valve regulators must be installed, operated
and maintained in accordance with federal,
state and local codes, rules and regulations
and Emerson Process Management Regulator
Technologies, Inc. instructions.
If the regulator vents gas or a leak develops in
the system, service to the unit may be required.
Failure to correct trouble could result in a
hazardous condition.
Installation, operation and maintenance
procedures performed by unqualified personnel
may result in improper adjustment and unsafe
operation. Either condition may result in
equipment damage or personal injury. Only
a qualified person shall install or service the
B Series regulator
CALIFORNIA PROPOSITION 65 WARNING
This product can expose you to chemicals
including lead, which is known to the State of
California to cause cancer, birth defects or other
reproductive harm. For more information, go to
www.P65Warnings.ca.gov.
Emerson.com
INTRODUCTION
Scope of the Manual
This manual provides instructions for the
installation, adjustment, and maintenance for
the B Series pressure regulators.
DESCRIPTION
The Type B regulator is a fully automatic
pressure regulating valve designed for
cryogenic service in the pressure build-up
circuit. Because the Type B may be used for
either cryogenic liquids or gases, it may be
installed either before or after the pressure
build-up coil.
SPECIFICATION DATA
Service: Cryogenic liquids and gases (pressure
reducing or build-up service)
Sizes: ¼", ⅜",
",
", 1", 1 ¼", 1 ½" and 2"
1
/
3
/
2
4
Connections: Threaded internal inlet and outlet
Body Material: Bronze
Temperature Rating: +150°F (339°K) to
-320°F (78°K)
Maximum Initial Pressure:
400 psi (27.6 bar)
© 2018 Emerson. All rights reserved.
GENERAL INSTALLATION INSTRUCTIONS
Install a Y-Type or equivalent strainer upstream
of the Type B. The built-in strainer screen is
secondary protection only.
The Type B regulator should be installed in the
horizontal position with the spring chamber up
or down. For other installation requirements
consult the factory. For ease of operation and
maintenance, it is suggested that manual
shutoff valves be installed upstream and
downstream from the valve. Before installing
the valve, the piping and the valve should be
thoroughly flushed out to remove any foreign
material. Install the valve with the inlet pipe
fitted to the inlet connection identified on the
valve body. Use a good pipe joint compound on
the male pipe threads and do not over tighten
the valve connections.
CONSTRUCTION
Bronze body, internal trim, and diaphragms;
Teflon seat, diaphragm gasket, and bottom
plug gasket; stainless steel pressure spring.
All parts are commercially cleaned for
oxygen service.
VCIOM-10796-EN 22/01

Advertisement

loading

Summary of Contents for Emerson CASH VALVE B Series

  • Page 1 State of 400 psi (27.6 bar) California to cause cancer, birth defects or other reproductive harm. For more information, go to www.P65Warnings.ca.gov. Emerson.com VCIOM-10796-EN 22/01 © 2018 Emerson. All rights reserved.
  • Page 2 CASH VALVE™ TYPE B ¼" TO 2" FOR CRYOGENIC SERVICE INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS OPERATING INSTRUCTIONS Servicing Diaphragm(s) and Pressure Spring Servicing the Cylinder, Piston, Strainer Screen, and Plug Gasket 1. Loosen the lock nut and turn the adjusting Adjusting the Delivery Pressure screw counterclockwise until the pressure 1.
  • Page 3 VCIOM-10796-EN © 2018, 2022 Emerson Electric Co. All rights reserved 01/22. Cash Valve is a mark owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners.