TESTING
designated time. The thermostat will start cooling or heating 1F for every 5
minutes before the next period. The maximum recovery time is 40 minutes.
PROGRAMMABLE FAN
Programmable Fan (Installer Option 04 = 0) is used to program the fan operation
along with the thermostat schedule. This is a very convenient feature that allows
selecting continuous (Always ON) or Automatic fan operation for each scheduled
event. When Programmable Fan is used, the fan operation can still be overridden
at the thermostat and will remain in the override mode until the next scheduled
event.
AUXILIARY CONTACTS
The Auxiliary Contacts (Installer Option 05) provide a selectable normally open or
normally closed dry contact output that works in conjunction with the
Programmable Fan feature when the thermostat is configured for programmable
mode. When the fan is in continuous (Always ON) mode, the auxiliary relay coil is
energized and de-energizes in Automatic mode. This feature can be used to
control peripheral devices such as an economizer or outside air damper.