High Balance Point; Adaptive Recovery - Jackson Systems T-32-TS Installation Manual

Hide thumbs Also See for T-32-TS:
Table of Contents

Advertisement

TESTING
To test the low balance point setting, set Option 16 above the displayed outdoor
temperature and force a call for heating. Only the auxiliary heat relay 'W1' should
energize. After testing, reset the low balance point setting to a normal operating
range.
HIGH BALANCE POINT (Heat Pump or Dual Fuel)
High balance point is designed to prevent the auxiliary heat 'W1' relay from
energizing when the outdoor temperature is above the balance point setting. To
test the high balance point setting, set Option 17 below the displayed outdoor
temperature and force a call for auxiliary heat. Only the compressor 'Y1' and/or
'Y1' and 'Y2' should energize. If the thermostat is placed in the E.Heat
(emergency heat) mode, the 'W1' relay will energize. After testing, reset the high
balance point setting to a normal operating range.

ADAPTIVE RECOVERY

Adaptive Recovery is only available in programmable mode (Installer Option 01 =
7) The Adaptive Recovery function of the T-32-TS permits the user to program a
time that a desired set temperature is required. The thermostat then calculates
the most energy efficient time to bring on the equipment to reach the setpoint at
46