Where a wall or other obstacle is in the path of outdoor unit's intake or exhaust airflow, follow the installation guidelines
below.
5SLY40/50ER
Wall facing one side
More than 100
Side View
Wall facing more than 1 side of obstacle
More
than 100
Allow more space for installation above with additional obstacle at top side and installation in series.
Do not install the unit at altitude over 2000m for both indoor and outdoor
Indoor
Outdoor
Max. allowable length, m
Max. allowable elevation, m
Liquid pipe, mm
Gas pipe, mm
Additional charge of refrigerant, g/m
(for piping length above 30m)

INSTALLATION OF THE OUTDOOR UNIT

More than 500
More
than
100
More than 100
Top View
! CAUTION

REFRIGERANT PIPING

1-9
More than 100
More than 500
5CEY40ER
5SLY40ER
75
30
9.5
15.9
50
Unit: mm
5CEY50ER
5SLY50ER
75
30
9.5
15.9
50