Electrical output specifications when running on battery power
MEGALINE
1250
Nominal output
voltage
Output
frequency
Nominal output
1250 VA
power VA
Active output power
with linear or non-
linear load P.F. 0,7
Total harmonic
distortion of output
voltage
Overload
capacity
Tolerated power
factor range of
applied load
DC-AC conversion
efficiency with
linear load P.F. 1
and charged
batteries:
•with 50% load
•with 75% load
•with 100% load
ATTENTION: There is a danger of explosion should the batteries be replaced with the wrong type.
!
Dispose of used batteries as per the instructions and precautions for their disposal on the battery label!
50 Hz / 60Hz ± 1% (autosensing and/or as selected by operator)
875 W
MEGALINE
2500
230 V ± 1%
2500 VA
1750 W
< 1%
160% for 15 seconds
from 0,7 to 1
80%
80%
80%
50
MEGALINE
3750
3750 VA
2625 W
5 - Specification
MEGALINE
5000
5000 VA
3500 W