MEGALINE
Nominal input
voltage
Input voltage
range
Nominal input
frequency
Nominal input
4,6A rms
current
Maximum input
5,75A rms
current
Distortion of input
current
Input power
factor
In-rush current
Number of input
phases
Line fuse
Battery charger
directly from mains
MEGALINE
With mains
operation
With battery
operation
Type of
operation
Electrical input specifications
MEGALINE
1250
from 184V to 264V with nom. load – from 100V to 264V with 50% of nom. load
50 Hz or 60 Hz +/-2% (autosensing and/or as selected by operator)
Output wave form
MEGALINE
1250
No break, on line UPS with passing neutral and double conversion
2500
230 V
8,9A rms
11,2A rms
THD
< 3%
> 0,99 dal 20% of nominal load
100% of nominal current
Single phase
25 AFF
0,8 A rms
2500
Sine wave
Sine wave
48
MEGALINE
3750
13,2A rms
16,6A rms
MEGALINE
3750
5 - Specifications
MEGALINE
5000
17,7A rms
22,2A rms
MEGALINE
5000
Need help?
Do you have a question about the MEGALINE 1250 RACK and is the answer not in the manual?