4 - Customising the UPS operating mode
Advanced mode
Sets the warning signal for the end of battery
autonomy using the remaining run time
(minutes)
Simple mode
Sets the warning signal for the end of battery
autonomy using the battery voltage.
There are two possible settings in the
Mode menu
If you select
Mode – Automatic thresholds
The UPS automatically calculates the voltage
thresholds based on the load: the UPS will
signal AUTONOMY RESERVE and END OF
AUTONOMY, respectively, below these.
If you select
Mode – Fixed thresholds
There are two options for this setting:
1) Reserve threshold
Sets the battery voltage threshold; the UPS will
signal AUTONOMY RESERVE below this
2) Exhaust threshold.
Sets the battery voltage threshold; the UPS will
signal END OF AUTONOMY below this.