Siemens sitrans LR 400 Instruction Manual page 92

Hide thumbs Also See for sitrans LR 400:
Table of Contents

Advertisement

The 2 function blocks (Level, Volume) return 5 bytes of data each:
Level
byte 1
Volume
byte 6
The first 4 bytes are the floating point representation (IEEE) of the variable. The variables
are the outputs of the function block. The default setting for the variable level is meters.
The default setting for the variable volume is m
variables by changing the settings of the function block. This is typically done using PDM.
The 5th byte is the status word and the list of possible values is given in the chart on
page 89.
The 5 bytes must be read consistently, in a contiguous chunk: they cannot be read byte by
byte, and cannot suffer an interrupt. If you are using an S7-300/400, you will need to use
SFC14 DPRD_DAT: Read Consistent Data of a Standard PD Slave.
If you select a Free Place module to fill one of the slots, this will affect the byte number.
Example 1:
Free
Place
Volume
Example 2:
byte1
Level
Free
Place
Page 88
Floating Point
byte 2
byte 3
byte 7
byte 8
Floating Point
byte 1
byte 2
byte 3
Floating Point
byte 2
byte 3
SITRANS LR 400 – INSTRUCTION MANUAL
byte 4
byte 9
3
. You can change the settings of the
byte 4
byte 4
Status
byte 5
byte10
byte10
Status
byte 5
Status
byte 5
7ML19985FH03

Advertisement

Table of Contents
loading

Table of Contents