Siemens sitrans LR 400 Instruction Manual page 23

Hide thumbs Also See for sitrans LR 400:
Table of Contents

Advertisement

Make the electrical connections as follows:
1.
Release the cover lock on the connection box with a 3 mm Allen key.
2.
Unscrew the cover from the connection box.
3.
Push the power cable and signal cable through the cable gland on the right of the
unit., up to the terminal strip. Lay the cable in a bend before the cable gland so that
moisture cannot enter the connection box.
4.
Connect the earth conductor of the power supply to the earth terminal
connection box. Adjust the cable length so that the earth conductor will be
disconnected last if you pull on the cable.
5.
In devices with ignition protection types II 1/2G EEx dem [ia] IIC T6 and II 1/2G EEx
dem [ib] IIC T6 or II 2G EEx dem [ia] IIC T6 and II 2G EEx dem [ib] IIC T6, mount the
cover for the power supply terminals.
6.
Tighten the cable screw gland and check the strain relief (pull and turn).
7.
In devices with ignition protection type II 1/2G EEx D IIC T6 or II 2G EEx d IIC T6,
replace unused screw-type cable glands with a certified dummy plug.
8.
Screw the cover onto the housing and tighten it without using a tool. The sealing
ring must be clean and undamaged.
9.
Mount the cover lock of the connection box cover.
10. Connect the earth terminal located between the screw-type cable glands to a
ground connection at your vessel by using a cable of a cross-section at least
2
2.5 mm
.
For error-free communication via the HART protocol, a load of at least 230 Ω must be
available in the signal circuit.
Warning:
To avoid short-circuits, do not connect a load resistance with bare wires in
the connection box.
The housing cover may not be unscrewed in a hazardous area when the
device is under voltage (power supply, digital outputs on external supply).
In devices with ignition protection types II 1/2G EEx dem [ia] IIC T6 and II 1/
2G EEx dem [ib] IIC T6 II 2G EEx dem [ia] IIC T6 and II 2G EEx dem [ib]
IIC T6, only the cover of the connection box may be unscrewed for test
purposes. The cover on the power supply terminals may not be removed!
7ML19985FH03
SITRANS LR 400 – INSTRUCTION MANUAL
in the
Page 19

Advertisement

Table of Contents
loading

Table of Contents