Endress+Hauser Levelflex FMP56 Operating Instructions Manual page 41

Guided wave radar profibus pa
Hide thumbs Also See for Levelflex FMP56:
Table of Contents

Advertisement

Levelflex FMP56, FMP57 PROFIBUS PA
Endress+Hauser
Mounting the electronics housing
A
122 (4.8)
158 (6.2)
 12
Mounting the electronics housing using the mounting bracket; dimensions: mm (in)
A
Wall mounting
B
Pipe mounting
Connecting the cable
Required tools:
Open-end wrench 18AF
A
C
r
= 100 (4)
min
 13
Connecting the cable. There are the following possibilities:
A
Angled plug at the probe
B
Angled plug at the electronics housing
C
Length of the remote cable as ordered
ø42...60
(1.65...2.36)
B
6 Nm
(4.42 lbf ft)
r
= 100 (4)
min
6 Nm
(4.42 lbf ft)
B
140 (5.5)
175 (6.9)
6 Nm
(4.42 lbf ft)
C
6 Nm
(4.42 lbf ft)
Mounting
A0014793
A0014794
41