Vacuuming And Charging Method - McQuay CE 10C Installation Manual

Ceiling/floor exposed convertible split type air conditioner
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
CE 40/50/61/62 CR
A
4WV
Terminal
Strip
OF
Indoor
Unit
COMP
L
N
IMPORTANT: (1) These values are for information only, they should be checked and selected to comply with the local and/
or national codes and regulations. They are also subjected to the type of installation and size of conductors
used.
(2) The appropriate voltage range should be checked with label data on the unit. ETL listed unit is only
applicable to 60Hz power supply only.
Ensure that the colors of wires on the outdoor unit and the terminal markings are the same as the indoor unit
respectively.
The pre-charged outdoor unit does not need any vacuuming or charging. However, once it is connected, the connecting
pipe line and the indoor unit need to be vacuumed before releasing the refrigerant (R22) from the outdoor unit.
Vacuuming Procedure For 2, 3 Way Valve (See Figure S)
1) Open the suction service port cap.
2) Manifold gauge connection:
Low side hose from manifold gauge to the suction
service port.
Service (center) hose from manifold gauge to the
vacuum pump.
3) Evacuate for approximately one hour (evacuation time
varies with pump capacity).
Confirm that the manifold gauge needle has moved
towards -30inHg (-76cmHg).
4) Close the low side valve on the manifold gauge, turn
off the vacuum pump and confirm that the gauge needle
does not move (approximately 3 minutes after turning
off the vacuum pump).
5) Disconnect the service hose from the vacuum pump.
6) After evacuation, open the valve stem of the discharge
and suction valve counter-clockwise for the gas to run
into the indoor unit.
7) Check the low side pressure after turning on the
compressor for 10 to 15 minutes.
Interconnection Cable
Power Supply
Cable
! Caution

VACUUMING AND CHARGING METHOD

1-9
A
4WV
OF
Terminal Strip
COMP
Outdoor Unit
L
N
R
S
The electrical power must be provided with
T
!
protection devices (circuit breaker or fuse)
N
with pole separation system, minimum
contact gap of 3mm.
Figure
S
For 2, 3 way valve
Indoor Unit
Liquid Side
Gas Side
Open
Suction Valve
Vacuum
Hi
Pump
Low
Close
Outdoor Unit
Discharge
Valve
Close
Close

Advertisement

Table of Contents
loading

Table of Contents