Mitsubishi QX10 User Manual page 22

I/o module type building block. melsec q series
Table of Contents

Advertisement

1
GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE
1 - 4
(5) Fuses installed to external terminals
It is recommended to install fuses to each external terminal. These fuses works to
prevent the external devices and the module from being burned when a short circuit
occurs in the load circuit of the QY22 or QY68A.
The following table lists the fuses whose operations have been checked and
ensured by Mitsubishi.
Module model
Fuse model
Rated current
Manufacturer
*1: Fuses that conform to Sheet 1 of IEC60127 are recommended.
*2: Fast blow fuses whose rated current is 3A are recommended.
(6) Precautions for using the transistor output module
(a) Action against reverse current
If a transistor output module is wired as shown below, reverse current flows in
an output element, causing a failure of the element.
When wiring a transistor output module, connect a diode as shown below.
• When connecting transistor output modules in parallel
Sink type
• When incorporating an additional circuit parallel to a transistor output
module
Additional circuit
OUT
Diode
COM
Sink type
1
QY22*
216 02.5
216 002
2.5A
2A
Littelfuse, Inc
Additional circuit
OUT
Diode
COM
Source type
MELSEC-Q
2
QY68A*
216 3.15
312 003
3.15A
3A
Source type
1 - 4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents