Qx42 Dc Input Module (Positive Common Type) - Mitsubishi QX10 User Manual

I/o module type building block. melsec q series
Table of Contents

Advertisement

2 INPUT MODULE SPECIFICATIONS

2.11 QX42 DC Input Module (Positive Common Type)

Specifications
Number of input points
Isolation method
Rated input voltage
Rated input current
Input derating
ON voltage/ON current
OFF voltage/OFF current
Input impedance
OFF to ON
Response
time
ON to OFF
Dielectric withstand voltage
Insulation resistance
Noise immunity
Protection degree
Common terminal arrangement
Number of occupied I/O points
Operation indicator
External connections
Applicable wire size
Applicable connector
Applicable connector/terminal block
converter module
Internal current consumption
(5VDC)
Weight
1: For the setting method, refer to Section 1.3.1.
2 : When using A6CON2 or A6CON3, refer to Chapter 7.
2 - 13
Type
24VDC (+20/-15%, ripple ratio within 5%)
1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter)
1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter)
560VAC rms/3 cycles (altitude 2000m)
10MΩ or more by insulation resistance tester
By noise simulator of 500Vp-p noise voltage, 1
and 25 to 60Hz noise frequency
First transient noise IEC61000-4-4: 1kV
32 points/common (common terminal: 1B01, 1B02, 2B01, 2B02)
64 points (I/O assignment is set as a 64-point input module.)
ON indication (LED), 32 point switch-over using switch
0.088 to 0.3mm
A6CON1, A6CON2, A6CON3, A6CON4 (optional)
A6TBXY36, A6TBXY54, A6TBX70
DC input module (Positive common type)
QX42
64 points
Photocoupler
Approx. 4mA
Refer to the derating chart.
19V or higher/3mA or higher
11V or lower/1.7mA or lower
Approx. 5.6kΩ
(Default: 10ms)
(Default: 10ms)
IP2X
40-pin connector
(For A6CON1 or A6CON4)
2
90mA (TYP. all points ON)
0.18kg
MELSEC-Q
Appearance
QX42
0 1 2 3 4 5 6 7
8 9 A B C D E F
0 1 2 3 4 5 6 7
8 9 A B C D E F
24VDC
4mA
1
1
s noise width
2
QX42
DISPLAY
F
L
2 - 13

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents