3.
Proximity to the clothes dryer vent – The clothes dryer vent
should not be located upwind from the unit.
4.
Ability to service – Side access panels of the unit should
not be closer than 24 inches to a structure so blower and
controls may be serviced.
5.
Sound transmission – Locate the unit away from bedroom
windows or other rooms where sound may be objectionable.
6.
Air Circulation – The outside coil sides should not be
closer than 24 inches to a structure that will restrict air flow
through the coil. The air discharge of the unit requires a 60-
inch clearance between the top of the unit and any
obstruction.See Figure 2.
7.
Wind direction – The hot condenser air must be discharged
up and away from the home or building, and if possible in a
direction with the prevailing wind.
8.
Relationship between building, sun and unit – If practical,
place the air conditioner in an area where the unit and the
ducts will be shaded from the afternoon sun (when the heat
load is the greatest).
9.
Defrost and Water Drainage - Water will run off the outdoor
coil when the heat pump defrosts during the heating
season. This water will run through the drain holes of the
heat pump base pan onto the ground below. A slight grade
away from the unit will improve drainage.
10. Average Winter Snow Depth - The heat pump must be
installed above the average snow depth to allow the
outdoor coil to drain properly.
Cinder blocks, if permitted by local codes, or a metal frame
may be used to support the unit above the snow. Insure
that the support does not obstruct drainage holes in the
base pan of the unit. Metal frame legs must be supported
Figure 3: Unit 4 Point Load Weight
Size
Weight (lbs.)
(Tons)
Shipping Operating
024
345
342
(2.0)
030
350
347
(2.5)
036
353
350
(3.0)
042
377
372
(3.5)
048
387
382
(4.0)
060
395
390
(5.0)
4
A
Left
D
Center of Gravity
4 Point Load Location (lbs.)
X
Y
A
21.75
14
79
21.75
14
80
23.5
15
80
23.5
15
100
28.75
16.25
94
28.75
16.25
96
by concrete pads. The heat pump must set level and
securely upon the support.
NOTE: If installing on blocks, the middle rail must be supported.
60"
Figure 2: Air Discharge Clearance

Site Preparation

After the site has been selected and prepared, using criteria
mentioned above, install the air conditioner support pad at the
selected site.
NOTE: This unit must be installed and operated on a level
surface. Failure to do so will result in condensate
drainage problems.

Clearances

All units require certain clearances for proper operation and
service. Refer to Table 3 for the clearances required for
construction, servicing and proper unit operation.
Rear
Y
CG
Front
B
C
D
71
91
101
72
92
103
84
95
91
69
83
120
94
97
97
96
99
99
B
Right
X
C