1.10 Instructions for installation and connection of the unit
Rated charge
Model
R-410A
(kg)
VCH 20A / VIR 25A
8,5
VCH 25A / VIR 25A
8,5
VCH 30A / VIR 40A
12
VCH 40A / VIR 40A
12
VCH 45A / VIR 45A
9.5 x 2
VCH 60A / VIR 60A
10.5 x 2
VCH 75A / VIR 75A
15 x 2
VCH 90A / VIR 90A
15 x 2
L: Maximum length on straight connection pipe sections.
L
: Maximum equivalent length of unit connection pipes.
E
1
: As of a total sum of 20 metres in length on straight connection pipe sections (horizontal and vertical) between units, a suction accumulator of at
least 7 litres must be fitted on the gas line.

1.10.6 Preparation and connecting to the various utilities

Electricity. Power and control
C A U T I O N
Loose connection terminals produce overheating of cables and terminals. The unit will work incorrectly
and there is a risk of fire.
Power Line
Power must be supplied to the unit through a specific electricity supply line with an exclusive power
control and differential breaker, installed in line with national and local regulations.
N O T E
For further information on this subject, always keep the current regulations for the country where the unit
is being installed at hand.
Make sure that the electricity supply line has enough capacity to power the unit. Its length, the cable
diameter and their protection (cover or jacket) should be appropriate for the unit.
Use a multimeter to check that the supply voltage
remains within the accepted limits.
To install the power cable, loosen the closures -1- by
1/4 turn and remove the electrical board panel.
36
No. of
Gas line diame‐
circuits
ter
1
1 ⅛" (28,5 mm)
1/2" (12,7 mm)
1
1 ⅛" (28,5 mm)
1/2" (12,7 mm)
1
1 ⅛" (28,5 mm)
5/8" (15,87 mm)
1
1 ⅛" (28,5 mm)
5/8" (15,87 mm)
2
1 ⅛" (28,5 mm)
1/2" (12,7 mm)
2
1 ⅛" (28,5 mm)
5/8" (15,87 mm)
2
1 ⅜" (35 mm)
7/8" (22 mm)
2
1 ⅜" (35 mm)
7/8" (22 mm)
Liquid line
Additional charge
diameter
(g/m)
112
112
170
170
112
170
333
333
1
L
L
E
(m)
(m)
1
50
60
1
50
60
50
60
50
60
50
60
50
60
50
60
50
60