Chapter 5
I/O Wiring

11-Series I/O Option Module

20-750-1132C-2R (24 Volts DC)
20-750-1133C-1R2T (24 Volts DC)
20-750-1132D-2R (120 Volts AC)
254
This section provides a description of the 11-Series I/O option module.
ATTENTION: When used in an Integrated Motion on EtherNet/IP networks
application for Firmware, versions 12 and later, the 11-series module must
be installed only in port 7.
Note that you cannot use the ATEX card with the 11-series I/O card in port 7
when used in an Integrated Motion on EtherNet/IP application.
Table 71 - Analog Input Mode Jumpers
Voltage Mode
1
1
P4
P5
2
2
Table 72 - TB1 Terminal Designations
Terminal Name
–10V
–10V reference
10VC
10V common
+10V
+10V reference
Sh
Shield
–10V
10VC
+10V
Sh
Ao0–
Ao0+
Ao0–
Analog out 0 (–)
Sh
Ai0–
Ai0+
Ao0+
Analog out 0 (+)
Sh
Di0
Di0P
Di1
Di1P
Di2
Di2P
Sh
Shield
Ip
Ic
EnC
EnNO
Ai0–
Analog input 0 (–)
Ai0+
Analog input 0 (+)
Sh
Shield
Rockwell Automation Publication 750-IN001P-EN-P - April 2017
Current Mode
1
1
P4
P5
2
2
Description
Negative 10V DC for analog inputs. 2 kΩ min
For (–) and (+) 10V references.
Positive 10V DC for analog inputs. 2 kΩ min
Terminating point for wire shields when an
EMC plate or conduit box is not installed.
Bipolar, ±10V, 11 bit and sign, 2 kΩ min
load.
4...20 mA, 11 bit and sign, 400 Ω max
load.
Terminating point for wire shields when an
EMC plate or conduit box is not installed.
(2)
Differential
, bipolar, 11 bit and sign.
Voltage Mode: ±10V at 88 kΩ input
impedance.
Current Mode: 0...20 mA at 93 Ω input
impedance.
Terminating point for wire shields when an
EMC plate or conduit box is not installed.