Power Wiring

Motor Overload Protection

Short Circuit Current Rating

Short Circuit Current Ratings
– Floor Mount Drives with
Cabinet Options
Table 27 - Short Circuit Current Ratings – 400V AC Input
Drive Catalog
Duty
kW
Number
Cycle
21G...C460
LD
315
ND
250
HD
200
21G...C540
LD
315
ND
315
HD
250
21G...C567
LD
355
ND
315
HD
250
21G...C650
LD
400
ND
355
HD
315
192
Class 10 motor overload protection according to NEC article 430 and motor
over-temperature protection according to NEC article 430.126 (A)(2). UL
508C File E59272.
The maximum short circuit rating is 200,000 A RMS symmetrical (only 20F
and 20G drives).
The actual short circuit rating is determined by the AIC rating of the installed
fuse or circuit breaker. See
Default ratings (no added protection) shown. A"•" indicates ratings that can
be achieved with additional protection.
Short Circuit Current Rating (kA)
Circuit Breaker
Circuit Breaker with Input Contactor
(1)
(1)
Only (P3)
(P3 with P11)
100
30
100
30 or
• 65 w/600 A Class J fuse
100
5 or
• 100 w/500...600 A Class J fuse
• 18 w/600...800 A Class L fuse
• 18 w/500 A CB
100
30
100
30
100
30 or
• 65 w/600 A Class J fuse
100
30
100
30
100
30 or
• 65 w/600 A Class J fuse
100
42
100
42
100
30
Rockwell Automation Publication 750-IN001P-EN-P - April 2017
page 192
for 21G drives.
Molded Case Switch Only
Molded Case Switch with Input Contactor
(2)
(P5)
(P5 with P11)
65 or
5 or
• 100 w/700...800 A Class L fuse
• 30 w/700...1200 A Class L fuse
• 30 w/700...1200 A CB
65
5 or
• 65 w/600 A Class J fuse
• 30 w/600...1000 A Class L fuse
• 30 w/600...1200 A CB
65
5 or
• 100 w/500...600 A Class J fuse
• 18 w/600...800 A Class L fuse
• 18 w/500 A CB
65 or
5 or
• 100 w/750...800 A Class L fuse
• 30 w/750...1300 A Class L fuse
• 30 w/800...1200 A CB
65 or
5 or
• 100 w/700...800 A Class L fuse
• 30 w/700...1200 A Class L fuse
• 30 w/700...1200 A CB
65
5 or
• 65 w/600 A Class J fuse
• 30 w/600...1000 A Class L fuse
• 30 w/600...1200 A CB
65 or
5 or
• 100 w/800 A Class L fuse
• 30 w/800...1300 A Class L fuse
• 30 w/800...1200 A CB
65 or
5 or
• 100 w/750...800 A Class L fuse
• 30 w/750...1200 A Class L fuse
• 30 w/800...1200 A CB
65
5 or
• 65 w/600 A Class J fuse
• 30 w/600...1000 A Class L fuse
• 30 w/600...1200 A CB
65 or
5 or
• 100 w/1000...1200 A Class L fuse
• 42 w/1000...1600 A Class L fuse
• 42 w/1000...1200 A CB
65 or
5 or
• 100 w/850...1200 A Class L fuse
• 42 w/850...1400 A Class L fuse
• 42w/900...1200 A CB
65 or
5 or
• 100 w/700...800 A Class L fuse
• 30 w/700...1200 A Class L fuse
• 30 w/700...1200 A CB