...2.2 Single Loop Controller (Templates 1 and 2)

351. 5
350. 0
PV – CSPt
Deviation
OP1
rAtO
1. 0 00
OP1
bIAS
5. 0 00
OP1
•1 With the Ramping Set Point function enabled (see Section 4.3, Set Points/ Ramp Rate), the
bargraph shows the actual (ramping) set point value and the digital display shows the target set
point value.
•2 Displayed only if template 2 selected and Ratio Display is enabled – see Section 5.2, Basic
Configuration and Section 5.7, Operator Configuration.
•3 Displayed only if template 2 selected and Bias Display is enabled – see Section 5.2, Basic
Configuration and Section 5.7, Operator Configuration.
•1
70
•2
•3
2 OPERATOR LEVEL...
Process Variable
Control Set Point
['SPLO' to 'SPHI' – see Section 5.5]
Adjustable in Local Control Only
Control Output
[0 to 100% (digital/relay outputs),
–10 to 110% (analog outputs)]
Adjustable in manual mode only. With on/off control
selected, 0% = control output off, 100% = control
output on. In manual mode, intermediate values can
be selected. These use 'time proportioning' with a
60s cycle time, e.g. 25% = 15s on, 45s off.
Remote Set Point Ratio
[0.001 to 9.999]
Remote set point value =
(ratio x remote set point input) + bias
Remote Set Point Bias
[In engineering units]
Continued...