Perform System Test; System Architecture - Honeywell Smile Room Connect SRC-10 Installation Instructions Manual

Table of Contents

Advertisement

Smile Room Connect SRC-10

6.6 Perform system test

When all the devices are connected to the SRC-10 and are installed,
perform a brief system test. You can perform a simple function test of the
heating system by setting the room set value temperature of each room
to the corresponding minimum and maximum temperatures. You can
then check whether the changes to the respective devices are displayed
and/have been performed. For battery-operated devices, it may take up
to four minutes for the device to respond to manual changes.

7 System architecture

Below, we have summarized several notes that affect the entire
system architecture.
1. If several radiator controllers (HR92) have been configured
in a room, then the connected radiator controller which was bound
first, is considered as the lead regulator.
2. As soon as one of the two T87RFxx or HCF82 room sensors has
been configured, this room sensor will be used for room regulation.
3. The battery status of the components is always displayed for the
entire room and reported at least once a day. After a battery
change, the status is shown immediately.
The following battery statuses are displayed:
No display
4. In order to increase the number of thermal actuators, several rooms
(1-8) can be assigned to one room to the underfloor heating controller
(HCE80).
53
Battery status low
Battery status OK
Battery status unknown
Installation Instructions
MU1H-0635GE51 R1016