6 DEDICATED INSTRUCTIONS

6.11 SWRITE Instruction

Set
Internal device
data
Bit
Word
(S1)
(S2)
(D1)
(D2)
(D3)
[Instruction
[Executing
symbol]
condition]
SWRITE
SWRITE
Setting data
Set data
Network number of the local station (1 to 239, 254)
Jn
254: The network designated by the valid module during other station
Start I/O signal of the local station's Ethernet net module.
Un
(00 to FE: The higher 2 digits of the 3-digit I/O signal.)
Head device of the local station that stores the control data.
(S1)
(S2)
Head device of the local station that stores data to be written.
(D1)
Head device of the target station to which data is written.
Local station device that is turned on for one scan by the completion of
(D2)
the instruction.
(D2) + 1 is turned on if the instruction execution completes abnormally.
Device of the target station that is turned on for one scan by the
(D3)
completion of the instruction. (Write notification device)
6 - 47
This instruction writes data to word devices of other stations.
MELSECNET/H,
MELSECNET/10
File register
Direct J \
Bit
Command
Command
Description
access.
The local devices and the file register for each program cannot be used as devices
used in setting data.
Applicable device
Special module
U \G
Word
JP.SWRITE
Jn
GP.SWRITE
Un
1
MELSEC-Q
Index register
Constant
Zn
(S1)
(S2)
(D1)
(D2)
(S1)
(S2)
(D1)
(D2)
1
Set by (
)
User
Character string
User, system
User
System
Others
K, H
(D3)
(D3)
Data type
Binary 16 bits
Device name
Bit
6 - 47