Appendices
Other Objects
This section lists other objects.
Index
Subindex
(hex)
(hex)
5000
Input Filter Setting
00
Number of Entries
01
Input Filter Value Setting
02
Input Filter Mode Setting
*1. The default value and data range for Number of Entries are as follows.
NX Units
NX-MD6121-5/MD6256-5
Other models
*2. The meaning of the set values for Input Filter Value Setting is as follows.
Set value
0
No Filter
1
0.25 ms
2
0.5 ms
3
1 ms
4
2 ms
5
4 ms
6
8 ms
7
16 ms
8
32 ms
9
64 ms
10
128 ms
11
256 ms
*3. The meaning of the set values for Input Filter Mode Setting is as follows.
Set value
0
Enable ON Filter and OFF Filter
1
Enable Only OFF Filter
A - 102
Default
Object name
value
*1
3
0
Default value
2
0
Meaning
Meaning
Data
Data range
Unit
type
*1
USINT
USINT
*2
0 to 11
USINT
*3
0/1
Data range
2 (fixed)
0 (fixed)
NX-series Digital I/O Unit User's Manual (W521)
I/O
Data
Acc
allo-
attri-
ess
cat-
bute
ion
RO
Not
pos-
sible
RW
Not
Y
pos-
sible
RW
Not
Y
pos-
sible