Media; Product Description; Overview - Viega G2101 Instructions For Use Manual

Gas ball valve
Table of Contents

Advertisement

2.2.2

Media

2.3

Product description

2.3.1

Overview

Gas ball valve
For planning, execution, modification and operation of gas installations,
observe the applicable regulations, see
regulations" on page 6 .
Use is possible in the gas installations described in the following:
Gas installations
n
low pressure range ≤ 100 hPa (100 mbar)
medium pressure range from 100 hPa (100 mbar) up to 0.1 MPa (1 bar)
Liquid gas installations
n
with liquid gas tank in medium pressure range downstream of
the pressure regulating device, 1st level on the
liquid gas tank > 100 hPa (100 mbar) up to a permitted operating
pressure of 0.5 MPa (5 bar)
with liquid gas tank in the low pressure range
≤ 100 hPa (100 mbar) behind the pressure regulating device,
2nd level
with liquid gas pressurised container (liquid gas bottles) < 16 kg
behind the small bottle pressure regulating valve
with liquid gas tank (liquid gas bottle) ≥ 16 kg
behind the large bottle pressure regulating device
Observe the applicable regulations, see
regulations" on page 6 .
The model is also suitable for the following media, amongst others:
Ä Chapter 2.1 „Standards and regulations" on page 6
Gases, see
n
Liquid gases, only in the gaseous state for domestic and commercial
n
Ä Chapter 2.1 „Standards and regulations"
applications, see
on page 6 .
Compressed air
n
Viega gas fittings conform with the requirements of the
applicable regulations. The gas fittings have been tested
and certified by the DVGW in accordance with the following
criteria, see Ä Chapter 2.1 „Standards and regulations"
on page 6:
Leak tightness
Higher thermal resistance (HTR)
Product information
Ä Chapter 2.1 „Standards and
Ä Chapter 2.1 „Standards and
8 from 12