Sensor Parameters
T-DELAY
Time Delay
Passive Infrared Sensitivity
WT
Walk-Through
Load Parameters
Load 1
ON Mode
AUTO-
ON
Operation*
Blink Warning
OFF
Daylighting
ON
NOTE: *Auto-OFF is enabled according to the sensor Time Delay when a sensor is bound to the load, regardless of whether the load
was turned on automatically with occupancy or manually using a switch.
** Max 8 loads using LMRC-100 series room controllers.
Loads do not operate as expected.
LEDs don't
1. Check to see that the sensor is connected to the DLM local Network.
light, display
2. Check for 24VDC input to the sensor: Plug in a different DLM device at the sensor location. If the device does
is off
not power up, 24VDC is not present.
• Check the high voltage connections to the room controller.
• If high voltage connections are good and high voltage is present, recheck DLM local Network connections
The wrong
Configure the sensor to control the desired lights using the Push n' Learn adjustment procedure.
lights are
controlled
LEDs turn ON
1. Make sure device is not in PnL.
and OFF but
2. Check load connections to room controller.
load doesn't
switch
FACTORY PRE-SET OPERATION
20 minutes
90%
OFF
Loads 2-8
or more**
MANUAL-ON
if switch is used.
AUTO-ON
if switch is not used.
OFF
OFF

TROUBLESHOOTING

between the sensor and the room controller.