INDOOR COIL ACCESS PANEL
Fig. 11 - - Typical Access Panel Locations
Fig. 12 - - Economizer Wiring
Fig. 13 - - Damper Assembly
FILTER ACCESS PANEL
C10004
Remove Hood Parts
Cut Plastic Ties
(2) Places
Economizer
C10005
Hood Parts
Plastic Tie Wrap
Qty (2)
Screws for Metal Tray
Qty (2)
C10006

Two Position Damper Hood Removal and Setup - -

Factory Option —
1. The hood is shipped in knock- - down form and
assembled to a metal support tray using plastic stretch
wrap. Located in the return air compartment, the
assembly's metal tray is attached to the basepan and
also attached to the damper using two plastic
tie- - wraps.
2. To gain access to the hood, remove the filter access
panel. (See Fig. 11.)
3. Locate the (2) screws holding the metal tray to the
basepan and remove. In order to remove the screws, it
may be necessary to remove the panel underneath the
two- - position damper. Remove the two screws. Locate
and cut the (2) plastic tie- - wraps securing the assembly
to the damper. (See Fig. 13.) Be careful to not damage
any wiring or cut tie- - wraps securing any wiring.
4. Carefully lift the hood assembly (with metal tray)
through the filter access opening and assemble per the
steps outlined in Economizer Hood and Two–Position
Hood.
5. If removed, reattach the panel under the damper.
Economizer Hood and Two- - Position Hood —
NOTE: If the power exhaust accessory is to be installed
on the unit, the hood shipped with the unit will not be
used and must be discarded. Save the aluminum filter for
use in the power exhaust hood assembly.
1. The indoor coil access panel will be used as the top of
the hood. If the panel is still attached to the unit, re-
move the screws along the sides and bottom of the
panel. See Fig. 14.
INDOOR
COIL
ACCESS
PANEL
Fig. 14 - - Indoor Coil Access Panel Relocation
2. Swing out indoor coil access panel and insert the
hood sides under the panel (hood top). Be careful not
to lift the panel too far as it might fall out. Use the
screws provided to attach the hood sides to the hood
top. Use screws provided to attach the hood sides to
the unit. See Fig. 15.
13
SIDE
PANEL
RAIN DEFLECTORS
TOP
PANEL
CAULK
HERE
INDOOR
COIL
ACCESS
PANEL
C10007