Economizer Hood And Two-Position Hood - Carrier WeatherMaker 50KCQ A04 Series Installation Instructions Manual

Single package rooftop heat pump with puron r-410a refrigerant
Hide thumbs Also See for WeatherMaker 50KCQ A04 Series:
Table of Contents

Advertisement

NOTCHES
BASEPAN
Fig. 13 — Location of Notches
Fig. 14 — Horizontal Duct Panels In Place
Step 8 — Install Outside Air Hood
ECONOMIZER
HOOD
SETUP – FACTORY OPTION
NOTE: Economizer and Two Position Damper are not available
as factory-installed options for size 04-06 single phase (-3 voltage
code) models.
1.
The hood is shipped in knock-down form and must be field-
assembled. The indoor coil access panel is used as the hood
top while the hood sides, divider and filter are packaged
together, attached to a metal support tray using plastic
stretch wrap, and shipped in the return-air compartment
behind the indoor coil access panel. The hood assembly's
NOTCHES
SCREWS
DUCT COVERS
SHEET METAL
FACE UP
BASEPAN
PACKAGE
REMOVAL AND
metal tray is attached to the basepan and also attached to the
damper using two plastic tie-wraps.
2.
To gain access to the hood, remove the filter access panel.
(See Fig. 15.)
FILTER ACCESS PANEL
Fig. 15 — Typical Access Panel Locations
3.
Locate the 2 screws holding the metal tray to the basepan and
remove. Locate and cut the 2 plastic tie-wraps securing the
assembly to the damper. (See Fig. 16.) Be careful to not dam-
age any wiring or cut tie-wraps securing any wiring.
Fig. 16 — Economizer Hood Parts Location
4.
Carefully lift the hood assembly (with metal tray) through
the filter access opening and assemble per the steps out-
lined in Economizer Hood, below.

ECONOMIZER HOOD AND TWO-POSITION HOOD

NOTE: If the power exhaust accessory is to be installed on the
unit, the hood shipped with the unit will not be used and must be
discarded. Save the aluminum filter for use in the power exhaust
hood assembly.
1.
The indoor coil access panel will be used as the top of the
hood. Remove the screws along the sides and bottom of
the indoor coil access panel. See Fig. 17.
15
COMPRESSOR
ACCESS PANEL
OUTDOOR-AIR OPENING AND
INDOOR COIL ACCESS PANEL
HOOD PARTS
PLASTIC TIE WRAP
QTY (2)
SCREWS FOR META
QTY (2)

Advertisement

Table of Contents
loading