Step 8 — Install Outside Air Hood
ECONOMIZER HOOD AND TWO-POSITION DAMPER
HOOD PACKAGE REMOVAL AND SETUP
OPTION)
NOTE: Economizer and two-position damper are not avail-
able as factory installed options for single phase (-3 voltage
code) models.
The hood is shipped in knock-down form and must be field
assembled. The indoor coil access panel is used as the
hood top while the hood sides, divider and filter are pack-
aged together, attached to a metal support tray using plastic
stretch wrap, and shipped in the return air compartment be-
hind the indoor coil access panel. The hood assembly's
metal tray is attached to the basepan and also attached to
the damper using two plastic tie-wraps.
1. To gain access to the hood, remove the filter access
panel. (See Fig. 9.)
FILTER ACCESS PANEL
Fig. 9 — Typical Access Panel Locations
2. Locate the (2) screws holding the metal tray to the
basepan and remove. Locate and cut the (2) plastic
tie-wraps securing the assembly to the damper. (See
Fig. 10.) Be careful to not damage any wiring or cut
tie-wraps securing any wiring.
Fig. 10 — Economizer and Two-Position Damper
Hood Parts Location
3. Carefully lift the hood assembly (with metal tray)
through the filter access opening and assemble per
the steps outlined in the following section Econo-
mizer Hood and Two-Position Hood.
527 01 2701 00
(
FACTORY
COMPRESSOR
ACCESS PANEL
OUTDOOR-AIR OPENING AND
INDOOR COIL ACCESS PANEL
HOOD PARTS
PLASTIC TIE WRAP
QTY (2)
SCREWS FOR METAL TRAY
QTY (2)
Specifications subject to change without notice.

ECONOMIZER AND TWO-POSITION HOOD

NOTE: If the power exhaust accessory is to be installed on
the unit, the hood shipped with the unit will not be used and
must be discarded. Save the aluminum filter for use in the
power exhaust hood assembly.
1. The indoor coil access panel will be used as the top
of the hood. Remove the screws along the sides and
bottom of the indoor coil access panel. See Fig. 11.
INDOOR
COIL
ACCESS
PANEL
Fig. 11 — Indoor Coil Access Panel Relocation
2. Swing out indoor coil access panel and insert the
hood sides under the panel (hood top). Use the
screws provided to attach the hood sides to the hood
top. Use screws provided to attach the hood sides to
the unit. See Fig. 12.
LEFT
HOOD
SIDE
19 1/16"
B
(483mm)
HOOD DIVIDER
Fig. 12 — Economizer Hood Construction
3. Remove the shipping tape holding the economizer
barometric relief damper in place (economizer only).
4. Insert the hood divider between the hood sides. See
Fig. 12 and 13. Secure hood divider with 2 screws on
each hood side. The hood divider is also used as the
bottom filter rack for the aluminum filter.
5. Open the filter clips which are located underneath the
hood top. Insert the aluminum filter into the bottom fil-
ter rack (hood divider). Push the filter into position
past the open filter clips. Close the filter clips to lock
the filter into place. See Fig. 13.
6. Caulk the ends of the joint between the unit top panel
and the hood top.
7. Replace the filter access panel.
TOP
PANEL
TOP
PANEL
CAULK
HERE
INDOOR
COIL
ACCESS
PANEL
TOP
PANEL
INDOOR COIL
ACCESS PANEL
SCREW
33 3/8"
(848mm)