RTU Open Controller System

The RTU Open controller is factory- - mounted in the
50TCQ unit's main control box, to the left of the CTB.
See Fig. 66. Factory wiring is completed through
harnesses connected to the CTB. Field connections for
RTU Open controller sensors will be made at the PCB
connectors on the RTU Open board. The factory- - installed
RTU Open controller includes the supply- - air temperature
(SAT) sensor. The outdoor air temperature (OAT) sensor is
included in the FIOP/accessory EconoMi$er
The RTU Open controller is an integrated component of
the
Carrier rooftop unit.
programming provides optimum performance and energy
3-Volt
Lithium
Battery
LonWorks
Option Card
Port
J15
Example set for
BACnet MS/TP
and 76.8K baud
(1, 2, and 4 ON)
Recommended for all
Protocol Selector
i-Vu Open installations
R
2 package.
Its internal
application
Board Power
J4
BO-1
BO-2
J13
J12
*Remove
SPT (temp input)
SPT (common)
both for 0-5V
SPT (offset input)
Fig. 65 - - RTU Open Multi- - Protocol Control Board
efficiency. RTU Open controller enables the unit to run in
100% stand- - alone control mode, Carrier's i- - Vu
network, or a Third Party Building Automation System
(BAS). On- - board DIP switches allow you to select your
protocol (and baud rate) of choice among the four most
popular protocols in use today: BACnet*, Modbus
Johnson N2 and LonWorks**. (See Fig. 65.)
Refer to Table 27, RTU Open Controller Inputs and
Outputs for locations of all connections to the RTU Open
controller board.
NOTE: The RTU Open controller acts as an intelligent
imbedded thermostat. A room thermostat cannot be used
with the RTU Open controller.
J1
J2
BO-3
BO-4
BO-5
J22
AO-2
BO-6
GND
(2-10V)
BO-7
BO-8
J17
Network Comm
J19
J20
BACnet, Modbus, or N2
(LON connection J15)
* BACnet is a registered trademark of ASHRAE (American Society of
Heating, Refrigerating and Air---Conditioning Engineers).
{
Modbus is a registered trademark of Schneider Electric.
** LonWorks is a registered trademark of Echelon Corporation.
50
R
(AO-1)
0-10VDC
J3
4-20mA
J5
J5
J22
VFD Output
J11
BO-6
(H) Humidimizer
BO-7
(Reversing Valve/High Speed Fan/Y3)
BO-8
(Power Exhaust)
J14
Open
{
,
C14129