Setting Limit Switches; Max. Limit For Filling Limit During Operation; Alarms A1 And A2 - Samson Media 6 Mounting And Operating Instructions

Differential pressure meter with lcd/led
Table of Contents

Advertisement

Turn write protection (switch 4) and span
protection (switch 3) ON.

6.5 Setting limit switches

6.5.1 Max. limit for filling limit dur-
ing operation
Note! The filling limit during operation set
over the software can only be changed over
the keys in the Media 6 version with LCD.
UCW Marker
Turn write protection (switch 4) OFF.
Press and hold down key until after 8 s
UCW appears at the top of the display
and underneath the associated % value.
Press key to confirm the display.
Press to reduce the value in steps of 1 %
or
Press to increase the value.
Press key to confirm new setting.
Turn write protection (switch 4) ON.

6.5.2 Alarms A1 and A2

Media 6 with LCD
Alarm A1 and A2 markers
Both limit switches are already set over the
software either as min. or max. contacts.
A1MIN or A1MAX as well as A2MIN or
A2MAX appear in the display.
Both limit switches must be set and con-
firmed separately.
Turn write protection (switch 4) OFF.
Press and hold down key until after 8 s
UCW appears at the top of the display.
or
needs to be pressed to switch
between alarm A1 or A2.
Press key to confirm selected alarm.
Press to reduce the value in steps of 1 %
or
Press to increase the value.
Press key to confirm new setting.
Press and hold down key again until
after 8 s UCW appears at the top of
the display.
or
needs to be pressed to switch over
to the second alarm that needs to be set.
Confirm selected alarm and set as
described above.
Turn write protection (switch 4) ON.
Setting
21
EB 9527-1 EN